What Insulation Thickness Do I Need?

Quick Answer

Walls: 90–100mm PIR • Roofs: 120–150mm • Floors: 70–100mm

Based on PIR board (λ = 0.022 W/mK) achieving Part L 2021 limiting U-values

Part L 2021 Limiting U-Values (England)

  • Walls: 0.18 W/m²K (new build), 0.30 W/m²K (existing)
  • Pitched roof (between rafters): 0.15 W/m²K
  • Flat roof: 0.15 W/m²K
  • Ground floor: 0.13 W/m²K (new build), 0.25 W/m²K (existing)

Thickness by Insulation Type

To achieve a wall U-value of 0.18 W/m²K:

  • PIR board (Celotex/Kingspan, λ 0.022): 90–100mm
  • Mineral wool (λ 0.035): 140–160mm
  • EPS (λ 0.032): 130–150mm
  • Phenolic foam (λ 0.020): 80–90mm

Roof Insulation Thickness

To achieve 0.15 W/m²K:

  • PIR between rafters: 120–150mm
  • Mineral wool at ceiling level: 270mm (two layers, 100mm + 170mm cross-laid)

Floor Insulation Thickness

  • PIR below screed: 70–100mm (depends on floor perimeter-to-area ratio)
  • PIR between joists: 100mm

Key Considerations

  • Always check with Building Control for your specific project
  • The actual U-value depends on the whole wall/roof build-up, not just the insulation
  • Thermal bridging at junctions reduces overall performance
  • Scotland, Wales, and Northern Ireland have different regulations