Part G Hot Water Safety Standards
Hot water storage temperatures, TMV requirements, Legionella prevention, and unvented cylinder regulations, referencing Approved Document G: Sanitation, Hot Water Safety and Water Efficiency (2015 edition incorporating 2016 amendments).
Hot Water Temperature Requirements (AD-G Section G3)
| Parameter | Requirement | Reason |
|---|---|---|
| Storage temperature | ≥ 60°C | Legionella prevention |
| Distribution temperature | ≥ 55°C at return / furthest point | Prevent bacterial growth in pipework |
| Bath outlet (new dwellings) | ≤ 48°C (via TMV) | Scald prevention |
| High-limit cut-out | ~90°C (non-self-resetting) | Over-temperature safety |
| T&P relief valve | 90-95°C / 6-10 bar | Pressure and temperature safety |
Legionella Temperature Risk Zones
| Temperature Range | Risk Level | Notes |
|---|---|---|
| Below 20°C | Low — bacteria dormant | Cold water should be kept below 20°C |
| 20°C to 45°C | High — rapid multiplication | Danger zone: avoid water sitting in this range |
| 45°C to 50°C | Moderate — some bacteria survive | Not hot enough to reliably kill bacteria |
| 50°C to 60°C | Low — bacteria die slowly | Takes hours to kill; not sufficient for storage |
| Above 60°C | Very low — bacteria killed quickly | Storage temperature target for safety |
Unvented Cylinder Safety Devices (AD-G Diagram 1)
| Device | Function | Standard |
|---|---|---|
| Thermostat | Controls operating temperature (60-65°C) | Integral to cylinder |
| High-limit thermal cut-out | Shuts off heat at ~90°C, requires manual reset | Non-self-resetting |
| Temperature & pressure relief valve | Opens at 90-95°C or 6-10 bar | BS 6283-2 |
| Expansion vessel / air gap | Accommodates water expansion when heated | Sized for cylinder volume |
| Tundish | Visible air break in T&P valve discharge | Within 500 mm of valve |
| Discharge pipe | Safely routes T&P discharge to safe point | Min. 1 pipe size larger than valve outlet |
G3 Notification Requirements
| Work Type | Notifiable? | Route |
|---|---|---|
| New unvented cylinder > 15 litres | Yes | Building Control or competent person scheme |
| Replacement unvented cylinder (like-for-like) | Yes | Building Control or competent person scheme |
| Vented cylinder installation | No (unless other notifiable work) | N/A |
| Unvented cylinder ≤ 15 litres | No | N/A (e.g. under-sink heaters) |
Related Calculators
Use the Hot Water Cylinder Calculator for sizing, or the Pipe Sizing Calculator for distribution pipework.
Always check the latest edition of Approved Documents on the Planning Portal (planningportal.co.uk) as regulations are updated periodically.
How We Calculate This
Frequently Asked Questions
Related Calculators
Concrete Mix Ratios
Standard UK concrete mix ratios explained with quantities per cubic metre and guidance on when to use each.
Insulation U-Values
Part L target U-values for walls, floors, roofs and windows with insulation thicknesses to achieve compliance.
UK Brick Dimensions
Standard UK brick sizes, coordinating dimensions and bricks per square metre for common bond patterns.
UK Cable Sizes
BS 7671 cable sizes and current ratings for common UK domestic circuits and installations.
Last updated: April 2026
All calculations are estimates. Verify with your supplier.