Part G Hot Water Safety Standards

Hot water storage temperatures, TMV requirements, Legionella prevention, and unvented cylinder regulations, referencing Approved Document G: Sanitation, Hot Water Safety and Water Efficiency (2015 edition incorporating 2016 amendments).

Hot Water Temperature Requirements (AD-G Section G3)

ParameterRequirementReason
Storage temperature≥ 60°CLegionella prevention
Distribution temperature≥ 55°C at return / furthest pointPrevent bacterial growth in pipework
Bath outlet (new dwellings)≤ 48°C (via TMV)Scald prevention
High-limit cut-out~90°C (non-self-resetting)Over-temperature safety
T&P relief valve90-95°C / 6-10 barPressure and temperature safety

Legionella Temperature Risk Zones

Temperature RangeRisk LevelNotes
Below 20°CLow — bacteria dormantCold water should be kept below 20°C
20°C to 45°CHigh — rapid multiplicationDanger zone: avoid water sitting in this range
45°C to 50°CModerate — some bacteria surviveNot hot enough to reliably kill bacteria
50°C to 60°CLow — bacteria die slowlyTakes hours to kill; not sufficient for storage
Above 60°CVery low — bacteria killed quicklyStorage temperature target for safety

Unvented Cylinder Safety Devices (AD-G Diagram 1)

DeviceFunctionStandard
ThermostatControls operating temperature (60-65°C)Integral to cylinder
High-limit thermal cut-outShuts off heat at ~90°C, requires manual resetNon-self-resetting
Temperature & pressure relief valveOpens at 90-95°C or 6-10 barBS 6283-2
Expansion vessel / air gapAccommodates water expansion when heatedSized for cylinder volume
TundishVisible air break in T&P valve dischargeWithin 500 mm of valve
Discharge pipeSafely routes T&P discharge to safe pointMin. 1 pipe size larger than valve outlet

G3 Notification Requirements

Work TypeNotifiable?Route
New unvented cylinder > 15 litresYesBuilding Control or competent person scheme
Replacement unvented cylinder (like-for-like)YesBuilding Control or competent person scheme
Vented cylinder installationNo (unless other notifiable work)N/A
Unvented cylinder ≤ 15 litresNoN/A (e.g. under-sink heaters)

Related Calculators

Use the Hot Water Cylinder Calculator for sizing, or the Pipe Sizing Calculator for distribution pipework.

Always check the latest edition of Approved Documents on the Planning Portal (planningportal.co.uk) as regulations are updated periodically.