Accessible WC Calculator - Doc M Wheelchair Toilet Dimensions
Check whether your wheelchair-accessible toilet layout meets Approved Document M and BS 8300-2:2018 requirements.
Internal clear width of the WC compartment
Internal clear length of the WC compartment
Effective clear width (Diagram 9). Doc M Table 2 minimum: 800mm new / 750mm existing
Next up: related pages
How We Calculate This
This calculator checks your proposed accessible toilet dimensions against the requirements of Approved Document M (Volume 2: Buildings other than dwellings, 2015 edition incorporating the 2024 amendments) and BS 8300-2:2018.
Dimension checks (unisex wheelchair WC)
- Room width: Minimum 1500mm (2000mm if it is the only toilet, para 5.10(e))
- Room length: Minimum 2200mm
- Turning space: 1500mm × 1500mm clear floor area (Diagram 18)
- Door width: Minimum effective clear width per Table 2 — 800mm new buildings, 750mm existing (right-angle approach to a ≥1500mm route); preferably outward-opening (5.10(g))
Grab rail positions
Grab rails are positioned per Doc M Diagram 19. Horizontal rails (including the drop-down rail) are set at 680mm above finished floor level. A drop-down rail is provided on the transfer side at 320mm from the centre line of the WC pan (para 5.10(j)); where the fixed wall rail is set at 400mm from the centre line, no additional drop-down rail is required (5.10(k)). Doc M 5.10(c)/(d) requires both left- and right-hand transfer layouts to be provided across a building’s accessible WCs.
WC types assessed
- Unisex Accessible WC: Full wheelchair accessible, Doc M Diagram 18 (1500 × 2200mm)
- Ambulant Disabled WC: For ambulant users with mobility aids, Doc M Diagram 21 (920 × 1465mm)
- Enlarged Compartment: Extra-space cubicle based on the ambulant compartment, Doc M 5.14(d) (1200mm wide × 1465mm deep)
Frequently Asked Questions
A unisex wheelchair-accessible WC per Approved Document M Volume 2 (Diagram 18) requires a minimum room size of 1500mm wide x 2200mm long. This allows space for a 1500mm x 1500mm wheelchair turning area, the WC pan, wash basin, and lateral transfer from wheelchair to WC. Where it is the only toilet in the building the width increases to 2000mm (para 5.10(e)). The door is governed by Table 2 of Approved Document M: its minimum effective clear width is 800mm in new buildings (750mm in existing buildings) for a door at right angles to an access route at least 1500mm wide. There is no separate 950mm door rule in Doc M.
A Doc M pack is a set of sanitaryware and fittings designed to meet Approved Document M requirements for accessible WCs. A standard pack includes: close-coupled WC pan with raised flush, wash basin, drop-down support rail, fixed support rails, back rest, mirror, shelves, coat hook, toilet roll holder, and alarm pull cord. Fittings are typically in contrasting colour (blue/white) for visually impaired users.
Doors to wheelchair-accessible WCs must open outwards or be sliding doors to ensure a wheelchair user is not trapped if they fall from their wheelchair inside the cubicle. An inward-opening door could block against a person on the floor, preventing rescue. The door must also be openable from outside in an emergency.
Ambulant disabled WCs are for people with mobility impairments who can walk (possibly with sticks or crutches) but do not use a wheelchair. Approved Document M Diagram 21 sets a minimum cubicle of 920mm wide x 1465mm deep with grab rails on the side wall and a vertical rail at the entrance. Wheelchair-accessible unisex WCs are larger (1500mm x 2200mm, Diagram 18) with a 1500mm turning area and lateral transfer space. Non-domestic buildings commonly need both types: a unisex wheelchair-accessible WC plus ambulant cubicles within the separate-sex washrooms.
Approved Document M Volume 2 expects at least one wheelchair-accessible unisex WC per floor in buildings other than dwellings, in addition to ambulant disabled cubicles within the standard WC blocks. Para 5.10(h) of Approved Document M states that a wheelchair user should not have to travel more than 40m on the same floor to reach a wheelchair-accessible unisex toilet (or more than 40m combined horizontal distance where it is reached on another floor by lift). The exact number depends on building use, occupancy and total WC provision.