Sewage Treatment Plant Calculator — What Size Do I Need?
Calculate the correct sewage treatment plant size for your property based on bedrooms or residents. Compliant with General Binding Rules (England) and BS EN 12566.
3-bed = 5 PE, 4-bed = 6 PE, 5-bed = 7 PE (min 5, then +1 per bedroom)
150 l/p/d is the British Water Flows and Loads 4 domestic loading
Enter a quoted price for reference
How We Calculate This
This calculator sizes a sewage treatment plant by the population equivalent (P) of your property, following the British Water Code of Practice Flows and Loads – 4, the recognised UK design method.
Population (P)
For a single house, use a minimum P of 5 for up to and including 3 bedrooms, then add 1 person per additional bedroom:
- 3-bedroom house = 5 PE
- 4-bedroom house = 6 PE
- 5-bedroom house = 7 PE
The calculated population is then rounded up to the nearest standard manufacturer unit (5, 6, 8, 10, 12 PE…). For multiple dwellings, Flows and Loads 4 also applies balancing reduction factors (×0.9 for 13–25 people, ×0.8 for 26–50 people).
Daily design flow
Daily flow = P × 150 litres/person/day. 150 l/p/d is the domestic hydraulic loading in Flows and Loads 4 (1 PE = 150 L/day flow, 60 g/day BOD). Higher figures may be used for properties with unusually high water use.
Plant capacity
A packaged treatment plant is notsized by a volume formula — its capacity is the manufacturer-tested PE rating under BS EN 12566-3. Select the unit whose rated PE meets or exceeds the calculated population. (The reference “primary-settlement volume” shown is the Approved Document H 2015 §1.18septic-tank volume rule — at least 2,700 litres for up to 4 users, plus 180 litres for each additional user — included only for comparison; it is not the treatment-plant rating.)
Standards
Sewage treatment plants must meet BS EN 12566-3 (packaged/site-assembled domestic wastewater treatment plants) and be UKCA/CE marked. The installation must comply with the General Binding Rules (England) — discharge to ground 2 m³/day or less, to surface water 5 m³/day or less — or hold an Environmental Permit. Building Regulations Approved Document H also applies.
Frequently Asked Questions
Related Calculators
Grey Water System Calculator
Calculate grey water recycling system storage tank, treatment unit and pump sizing.
Manhole Calculator
Calculate manhole rings, benching, cover and frame for inspection chambers.
Land Drain Calculator
Calculate perforated pipe, gravel and geotextile for land drainage systems.
ACO Drain Calculator
Calculate channel drain lengths, end caps, outlets and gratings.
Was this calculator helpful?
Last updated: February 2026
Verified against UK standards · estimates only, confirm with your supplier.