Room Ventilation Calculator

Calculate Part F ventilation requirements: trickle vent equivalent area, extract rates for wet rooms, and purge ventilation for 4 air changes per hour.

Determines extract rate and vent size

Each window needs a trickle vent

Mechanical extract fan installed

Intermittent fan vs continuous MVHR

How We Calculate This

This calculator determines the ventilation requirements for rooms under Building Regulations Part F (Ventilation). It covers trickle vent sizing, mechanical extract rates, and purge ventilation capacity.

The formula

Purge rate = Room volume × 4 ACH
Purge opening = Floor area ÷ 20
Extract rate = Part F table by room type
Trickle vent EA = 5,000 mm² (habitable) or 2,500 mm² (wet rooms)

Part F extract rates

  • Kitchen: 60 l/s intermittent or 13 l/s continuous
  • Bathroom: 15 l/s intermittent or 8 l/s continuous
  • Utility: 30 l/s intermittent or 8 l/s continuous
  • WC: 6 l/s intermittent or 6 l/s continuous