Spray Foam Calculator — Thickness, Coverage & U-Value

Calculate spray foam insulation thickness for target U-value. Compares open vs closed cell foam with coverage per kit and ventilation gap requirements.

Roof, wall, or floor area

Thermal resistance of existing construction

Include ventilation gap (open cell roof)

50mm gap above open cell foam

How We Calculate This

This calculator determines spray foam thickness needed to achieve a target U-value, then calculates the volume and number of kits required for the job.

The formula

Required R-value = (1 ÷ Target U) - Existing R - Surface resistances

Foam thickness = Required R × Lambda × 1000 (mm)

Volume = Area × Thickness × (1 + Wastage)

Kits = Board-feet needed ÷ kit board-feet rating (1 board-foot = 1 ft² at 1 inch = 0.00236 m³)

Surface resistances follow BR 443 / BS EN ISO 6946 by heat-flow direction: walls 0.13 + 0.04 = 0.17, roofs (upward) 0.10 + 0.04 = 0.14, floors (downward) 0.17 + 0.04 = 0.21 m²K/W.

For example, a 50 m² roof at target 0.16 W/m²K with closed cell (λ = 0.022) and 0.5 m²K/W of existing construction: R needed = (1 ÷ 0.16) - 0.5 - 0.14 = 5.61. Thickness = 5.61 × 0.022 × 1000 ≈ 124mm. With 5% wastage, volume = 50 × 0.124 × 1.05 = 6.51 m³ ≈ 2,759 board-feet, so about 5 closed-cell kits at 605 board-feet each. Confirm the board-feet rating of the kit you buy — kit sizes vary by brand.

Frequently Asked Questions

Was this calculator helpful?

Last updated: June 2026

Verified against UK standards · estimates only, confirm with your supplier.