Kitchen Extraction Calculator — Part F Ventilation Rates
Calculate kitchen extraction rates for cooker hoods and mechanical ventilation per Part F.
Internal kitchen length
Internal kitchen width
Floor to ceiling height
Yes → 30 l/s; No (no hood, hood elsewhere, or recirculating) → 60 l/s per ADF 2021 Table 1.1
Straight-line duct run length
Each bend adds ~1.5m effective length
Recirculating mode — does not extract to outside, so does not comply with Part F on its own
Next up: related pages
How We Calculate This
This calculator determines the required kitchen extraction rate based on room volume, kitchen type and cooking appliance, then checks ducting adequacy and Part F compliance.
How it works
- Room volume: Length x width x ceiling height in cubic metres
- Extraction rate: Domestic per ADF 2021 Table 1.1 — 30 l/s where a cooker hood over the hob extracts to outside, or 60 l/s where there is no hood, the hood does not extract to outside, or the extract is sited elsewhere (13 l/s continuous, Table 1.2). Commercial uses air changes per hour as an indicative screen only
- Effective duct length: Actual length plus ~1.5m per 90° bend (indicative; 1–2m per bend is the common guideline), with a roof termination adding a further bend equivalent
- Pressure loss: Indicative estimate from duct diameter and effective length, plus a terminal allowance for roof cowls — not a standard-derived figure
- Fan sizing: Based on the required extraction rate plus a duct-resistance allowance; confirm the fan delivers the rate at the system pressure from its airflow-vs-pressure curve
- Noise: Indicative estimate from fan type, duct diameter and back-pressure — use the manufacturer's declared sound data
Domestic figures reference Approved Document F Volume 1 (2021), Tables 1.1 and 1.2. Commercial sizing should follow CIBSE Guide B, DW/172 (BESA) and BS EN 16282-1; the air-change figure here is only a rough screen, not a design method.
Frequently Asked Questions
Approved Document F Volume 1 (2021) Table 1.1 sets the minimum intermittent kitchen extract rate at 30 l/s where a cooker hood over the hob extracts to outside, or 60 l/s where there is no cooker hood, the hood does not extract to outside (e.g. recirculating), or the extract is sited elsewhere in the kitchen. For continuous mechanical extract the minimum is 13 l/s (Table 1.2). A recirculating hood on its own does not satisfy Part F (note to Diagram 1.2) — a ducted extract to outside is still required, at the 60 l/s rate. These rates apply to new builds and extensions in England; Scotland (Section 3 Technical Handbook) and Wales have similar but not identical requirements.
A 150mm (6 inch) rigid duct is recommended for most domestic cooker hood installations. This minimises pressure drop and noise. A 125mm duct is only acceptable for very short, near-straight runs — keep the effective duct length (the straight run plus roughly 1.5m for each 90-degree bend) to about 3m or less, which in practice means a short run with at most one or two bends, not both. Avoid 100mm ducting for cooker hoods as it restricts airflow significantly. Always check the hood manufacturer's instructions (many require 150mm and reducing the diameter can invalidate the warranty), and use rigid or semi-rigid ducting rather than flexible aluminium hose, which causes turbulence and grease build-up.
Each 90-degree bend in the ducting adds approximately 1.5 metres of equivalent duct length in terms of air resistance. A 45-degree bend adds roughly 0.75m equivalent. For optimal performance, minimise the number of bends and keep the total effective duct length (actual length plus bend equivalents) as short as possible. Most cooker hood manufacturers recommend a maximum effective duct length of 5-6m.
Yes, recirculating hoods require activated carbon filters to remove cooking odours before returning air to the kitchen. These filters need replacing every 3-6 months depending on usage. Note that a recirculating hood does not meet Part F kitchen extract requirements on its own (note to Diagram 1.2, ADF 2021) — it does not remove cooking moisture or combustion products from the dwelling. You still need a ducted extract to outside (60 l/s intermittent, or 13 l/s continuous) plus background ventilation.
As an indicative screen, a commercial kitchen with cooking needs a minimum of about 30 air changes per hour (CIBSE Guide B); roughly 20 ACH suits a non-cooking preparation area. Gas-fired equipment needs higher rates due to combustion products. However, air changes alone are not the design method — commercial kitchens should be sized by the thermal/canopy approach in DW/172 (BESA) and BS EN 16282-1, which determines the extract from the heat and effluent released by the appliances. Under DW/172 (Canopy Dimensions section) the canopy plan dimensions must exceed the cooking equipment by a minimum of 250mm on each free side (measured to the inside of the condensation channel), increasing to 600mm at the front for combination ovens and 300mm for solid-fuel appliances.