Condensate Pipe Calculator — Boiler Drainage

Calculate maximum condensate pipe runs, minimum fall, external insulation requirements, and termination options per BS 6798 and Building Regulations.

Total horizontal pipe run

Condensate pipe outer diameter

Boiler rated output

Where condensate pipe discharges

External Run

Does the pipe run outside the building?

How We Calculate This

This calculator helps plan condensate pipe installations for condensing boilers in accordance with BS 6798 and manufacturer guidance. It checks run lengths, fall requirements, and external installation compliance.

Key rules

  • Maximum run: 3m (21.5mm), 6m (32mm), 10m (40mm)
  • Minimum fall: 2.5° (~44mm/m)
  • External runs: Minimum 32mm, insulated, keep short
  • Condensate rate: ~2L/hr per 30 kW condensing boiler
  • Termination: Soil stack, trapped gulley, or limestone soakaway