Condensate Pipe Calculator — Boiler Drainage
Calculate maximum condensate pipe runs, minimum fall, external insulation requirements, and termination options per BS 6798 and Building Regulations.
Does the pipe run outside the building?
How We Calculate This
This calculator helps plan condensate pipe installations for condensing boilers in accordance with BS 6798 and manufacturer guidance. It checks run lengths, fall requirements, and external installation compliance.
Key rules
- Maximum run: 3m (21.5mm), 6m (32mm), 10m (40mm)
- Minimum fall: 2.5° (~44mm/m)
- External runs: Minimum 32mm, insulated, keep short
- Condensate rate: ~0.15 L/kWh at full fire (BS 6798 / BRE DER) — e.g. 4.5 L/hr for a 30 kW boiler
- Termination: Soil stack, trapped gulley, or limestone soakaway