Condensate Pipe Calculator — Boiler Drainage
Calculate maximum condensate pipe runs, minimum fall, external insulation requirements, and termination options per BS 6798 and Building Regulations.
Total horizontal pipe run
Boiler rated output
Does the pipe run outside the building?
Min fall 2.58° ≈ 45mm/m (HHIC / BS 6798); some makers require 3° ≈ 52mm/m
External pipe insulation thickness
Next up: related pages
How We Calculate This
This calculator helps plan condensate pipe installations for condensing boilers in accordance with BS 6798 and manufacturer guidance. It checks run lengths, fall requirements, and external installation compliance.
Key rules
- Maximum run: 3m (21.5mm, firmly cited); 6m (32mm) and 10m (40mm) are typical trade sizing convention — follow the boiler manual
- Minimum fall: ~45mm/m (2.58°) per HHIC / BS 6798; some makers require 3° (52mm/m)
- External runs: Minimum 32mm, insulated, keep short (≤3m); trace heating in exposed locations
- Condensate rate: ~0.10 L/kWh at full fire (HHIC: ~2 L/hr for an efficiently working boiler) — e.g. 3.0 L/hr for a 30 kW boiler
- Termination: Soil stack, trapped gulley, or limestone soakaway
Frequently Asked Questions
For 21.5mm pipe the firmly-cited limit is 3 metres horizontal (HHIC / manufacturer guidance). 32mm (≈6 metres) and 40mm (≈10 metres) gravity-run figures are typical trade sizing convention rather than a verbatim BS 6798 limit, so always check the boiler manufacturer’s instructions. These limits assume a minimum fall of about 45mm per metre (2.58 degrees). Longer runs require a larger diameter pipe.
HHIC and BS 6798 quote a minimum fall of about 45mm per metre (2.58 degrees) of horizontal run; some manufacturers (e.g. Worcester Bosch) specify 3 degrees (52mm per metre), so follow the boiler manual. Adequate fall ensures condensate flows freely by gravity without pooling, which could freeze in cold weather or cause the boiler to lock out.
External condensate runs should be avoided where possible. If unavoidable, use minimum 32mm pipe, keep the external run as short as possible (ideally under 3 metres), insulate with minimum 19mm waterproof insulation, and consider trace heating in exposed locations.
Where no suitable drain is available, BS 6798 allows condensate to discharge into a purpose-built soakaway. A typical detail (e.g. McAlpine SOAK1GR, sold as BS 6798:2014 compliant) is a hole about 400mm deep × 300mm diameter, filled with 10mm limestone chippings to neutralise the acidic condensate (pH 3-4), with the pipe cut at 45° and inserted at least 25mm in, located at least 500mm from any building or footing.
Condensate freezing is the most common cause of boiler breakdown in winter. The acidic condensate (pH 3–4) has a slightly lower freezing point than water but still freezes in sustained sub-zero temperatures. Prevention includes insulation, trace heating, minimising external runs, and ensuring adequate fall. See our Condensing Efficiency Calculator to check your boiler is running in condensing mode.