Heating Cleaner Calculator — Chemical Dosing

Calculate system cleaner dose, circulation time, flush volume, and inhibitor re-dose for heating system maintenance per BS 7593:2019+A1:2024.

Total heating system water volume

How We Calculate This

This calculator determines the chemical dosing requirements for heating system cleaning and treatment in accordance with BS 7593:2019+A1:2024 and manufacturer guidance.

Dosing method

  • Cleaner dose: System volume ÷ 100 (1%, e.g. Sentinel X400 / Fernox F3 — 1 L per 100 L)
  • Descaler dose: System volume ÷ 100 standard (1%), or ÷ 50 for heavy fouling (2%, Sentinel X800 Jetflo)
  • Biocide dose: System volume ÷ 300 (0.3%, Sentinel X700 — 1 L per 300 L)
  • Circulation: Minimum time at full operating temperature (cleaner ≥ 2 h per the Sentinel X400 datasheet; BS 7593:2019+A1:2024 requires cleaning to the manufacturer’s instructions)
  • Flush volume (approx): System volume × number of cycles (estimate ≈ 1 system volume per cycle)
  • Inhibitor dose: System volume ÷ 100 (Sentinel X100 / Fernox F1 — 1 L per 100 L)