Pressurised Safety Calculator — G3 Discharge Sizing

Calculate PRV settings, expansion vessel acceptance, T&P valve discharge pipe sizing, and tundish requirements per Building Regulations Part G3.

Measured mains water pressure

How We Calculate This

This calculator sizes the safety components for pressurised (unvented) hot water systems in accordance with Building Regulations Approved Document G3 (the discharge-pipe sizing table lives in G3 itself; the underlying water-supply standards are BS 8558 / BS EN 806, which superseded the withdrawn BS 6700).

Component sizing

  • PRV: Set to reduce incoming pressure to a safe cold working pressure (typically 3 bar)
  • Expansion vessel: Acceptance-volume method. Expansion volume = system volume × 0.0195 (water 10°C→65°C); vessel = expansion volume ÷ acceptance factor, where acceptance factor = 1 − Ppre-charge/Prelief in bar absolute, then a 10% margin and round up to a standard size (2/5/8/12/18/24 L)
  • Pre-charge: Equal to the static cold-fill (cold working) pressure, set about 0.2 bar below it
  • T&P valve: Domestic standard 90°C / 7 bar (BS EN 1490; settings 4/7/10 bar)
  • D1 pipe: Same size as the T&P valve outlet (15 or 22mm), max 500mm long
  • D2 pipe: At least one size larger than D1 (22 or 28mm)
  • Tundish: Vertical, in the same space as the cylinder and within 500mm of the T&P valve, visible for inspection