Stove Flue Calculator — Approved Document J

Calculate flue diameter from stove kW, height for adequate draw, twin wall vs liner selection, and ventilation air requirements per Approved Document J.

Stove rated heat output (AD J covers solid-fuel up to 50kW)

Effective flue height (stove outlet to terminal); AD J para 2.8 indicates 4.5m can be satisfactory

Room volume (guideline only — AD J sets no minimum room volume)

DEFRA-Exempt Appliance

Clean-Air-Act / DEFRA-exempt stove burning smokeless fuel (allows 125mm at ≤20kW)?

Airtight Dwelling (≤5 m³/h·m²)

Modern airtight home (design air permeability ≤5.0 m³/h·m²)? Removes the 5kW vent deduction

Direct Air Supply

Stove connected to a dedicated external air supply?

How We Calculate This

This calculator sizes stove flues in accordance with Approved Document J (Combustion Appliances and Fuel Storage Systems). It determines the minimum flue diameter, height for adequate draw, and ventilation requirements.

Approved Document J rules

  • Flue diameter (Table 2): 150mm for a closed appliance up to 30kW (125mm if DEFRA-exempt and ≤20kW); 175mm for above 30kW up to 50kW
  • Flue height (para 2.8): 4.5m can be satisfactory; shorter flues need a BS EN 13384-1 calc. Terminate ≥600mm above the ridge if within 600mm of it, otherwise ≥2300mm horizontally and ≥1000mm above where it passes through (Diagram 17)
  • Draught: rule of thumb ~3 Pa per metre of warm-flue height — verify by BS EN 13384-1 or measure on commissioning
  • Ventilation (Table 1, no stabiliser): 550 mm² per kW above 5 kW in a leaky home; 550 mm² per kW of total output (no 5kW deduction) in an airtight home ≤5.0 m³/h·m²
  • Room volume: AD J sets no minimum — ventilation is by free area, not room size
  • CO alarm (para 2.34): required for solid-fuel appliances, to BS EN 50291

Frequently Asked Questions

Was this calculator helpful?

Last updated: March 2026