TradeCalculator.co.uk
Thermal Store Calculator — Buffer Tank Sizing
Size buffer tanks and thermal stores for heat pump anti-cycling protection. Calculate buffer volume, stored energy and charge/discharge times.
Minimum compressor run time (20 mins typical)
Current / minimum heat demand on system
System flow temperature — lower flow (35–45°C) gives a higher COP
Temperature swing in buffer (5-10°C typical)
Next up: related pages
How We Calculate This
This calculator sizes buffer tanks and thermal stores to prevent heat pump short-cycling. It calculates the minimum volume needed based on the surplus energy that must be absorbed during the minimum compressor run time.
Formulas
- Surplus kW: Heat pump output − current heat demand
- Anti-cycling volume: (Surplus kW × run time × 60) ÷ (4.186 × ΔT)
- Minimum-volume floor (source-aware): about 25 L/kW for air source (BS EN 14511 defrost guidance), about 10 L/kW for ground source (Kensa GSHP). The result is the larger of this floor and the anti-cycling volume. BS EN 15450:2007 gives a wider 12–35 L/kW design range
- Energy stored: (Volume × 4.186 × ΔT) ÷ 3600 kWh
Pressure rating is set by the sealed system’s working pressure, not the water temperature: a standard heat-pump buffer on the sealed heating circuit is rated 3-bar working / 6-bar test (the 3-bar PRV is the recognised domestic value under BS EN 12828, whose maximum operating pressure is 6 bar). This is the sealed heating circuit, not an unvented DHW cylinder, so it is governed by BS EN 12828 rather than Approved Document G3. Higher-rated vessels (6/10 bar) are product options, not a function of flow temperature.
Frequently Asked Questions
Heat pumps should run for minimum cycles of 10–20 minutes to operate efficiently. If the heat demand is less than the heat pump output (e.g. mild weather or few zones calling), the surplus energy needs somewhere to go. A buffer tank absorbs this surplus, preventing short-cycling that damages the compressor. Use our Heat Pump Sizing Calculator to size the heat pump correctly first.
Take the larger of two figures. First, the anti-cycling volume: Buffer volume = (surplus kW × minimum run time × 60) ÷ (4.186 × ΔT). Second, a minimum-volume floor that depends on the heat-pump type — about 25 litres per kW for an air-source pump (BS EN 14511 guidance, to cover defrost), or about 10 litres per kW for ground source (Kensa). BS EN 15450:2007 gives a wider 12-35 L/kW design range. Worked example: an 8 kW air-source pump with 6 kW demand, a 20-minute minimum run time and a 10°C ΔT gives an anti-cycling volume of about 57 litres, but the 25 L/kW air-source floor (8 × 25 = 200 litres) governs, so you would fit a 200-litre buffer.
A buffer tank is a simple volume of water added to the heating circuit to prevent short-cycling. A thermal store is more sophisticated — it stores heat from multiple sources (heat pump, solar, wood burner) and can supply both heating and domestic hot water via plate heat exchangers.
The buffer tank operates at the heating system temperature, typically 35-50°C for a heat pump. The ΔT across the buffer is usually 5-10°C. Higher flow temperatures and larger ΔT allow more energy storage in a smaller vessel, but reduce heat pump efficiency (COP).
Yes. A thermal store with multiple coils or connections can accept heat from a heat pump, solar thermal, wood burner, and even off-peak electric immersion. Priority controls determine which source charges the store first, typically: solar → heat pump → backup immersion.
Related Calculators
Was this calculator helpful?
Last updated: June 2026
Verified against UK standards · estimates only, confirm with your supplier.