Skip to content

Thermal Store Calculator — Buffer Tank Sizing

Size buffer tanks and thermal stores for heat pump anti-cycling protection. Calculate buffer volume, stored energy and charge/discharge times.

Minimum compressor run time (20 mins typical)

Current / minimum heat demand on system

System flow temperature — lower flow (35–45°C) gives a higher COP

How We Calculate This

This calculator sizes buffer tanks and thermal stores to prevent heat pump short-cycling. It calculates the minimum volume needed based on the surplus energy that must be absorbed during the minimum compressor run time.

Formulas

  • Surplus kW: Heat pump output − current heat demand
  • Anti-cycling volume: (Surplus kW × run time × 60) ÷ (4.186 × ΔT)
  • Minimum-volume floor (source-aware): about 25 L/kW for air source (BS EN 14511 defrost guidance), about 10 L/kW for ground source (Kensa GSHP). The result is the larger of this floor and the anti-cycling volume. BS EN 15450:2007 gives a wider 12–35 L/kW design range
  • Energy stored: (Volume × 4.186 × ΔT) ÷ 3600 kWh

Pressure rating is set by the sealed system’s working pressure, not the water temperature: a standard heat-pump buffer on the sealed heating circuit is rated 3-bar working / 6-bar test (the 3-bar PRV is the recognised domestic value under BS EN 12828, whose maximum operating pressure is 6 bar). This is the sealed heating circuit, not an unvented DHW cylinder, so it is governed by BS EN 12828 rather than Approved Document G3. Higher-rated vessels (6/10 bar) are product options, not a function of flow temperature.

Frequently Asked Questions

Was this calculator helpful?

Last updated: June 2026

Verified against UK standards · estimates only, confirm with your supplier.