Standard domestic circuit specifications per BS 7671 18th Edition: cable sizes, MCB ratings, maximum lengths, and protective device requirements.

Standard Domestic Circuits

CircuitCable SizeMCB RatingMCB TypeRCD Required
Lighting (6A)1.0 mm² or 1.5 mm²6ABYes (30 mA)
Ring final (sockets)2.5 mm²32ABYes (30 mA)
Radial (sockets, ≤50 m²)2.5 mm²20ABYes (30 mA)
Radial (sockets, ≤75 m²)4.0 mm²32ABYes (30 mA)
Immersion heater2.5 mm²16ABYes (30 mA)
Cooker (≤13.5 kW)6.0 mm²32ABYes (30 mA)
Cooker (>13.5 kW)10.0 mm²45ABYes (30 mA)
Shower (up to 9 kW)6.0 mm²40ABYes (30 mA)
Shower (9-10.8 kW)10.0 mm²45ABYes (30 mA)
Smoke/heat alarms1.0 mm² or 1.5 mm²6ABNo (dedicated circuit)
Outdoor socket2.5 mm²16A or 20ABYes (30 mA)
EV charger (7 kW)6.0 mm² or 10.0 mm²32AB or CYes (Type A or DC)

Cable Current Ratings (Clipped Direct, PVC T&E)

Cable Size (mm²)Clipped Direct (A)In Insulation (A)In Conduit/Trunking (A)
1.015.511.513.5
1.52014.517.5
2.5272024
4.0372732
6.0473441
10.0654657
16.0876276

Values from BS 7671 Table 4D5, Installation Method C (clipped direct). Derating factors apply for grouping, ambient temperature, and thermal insulation.

Related Calculators

Use the Cable Sizing Calculator for volt drop and derating, or the Lighting Circuit Calculator for domestic lighting design. See also the BS 7671 glossary entry and the Part P glossary entry.