Part G Hot Water Safety Standards
Hot water storage temperatures, TMV requirements, Legionella prevention, and unvented cylinder regulations, referencing Approved Document G: Sanitation, Hot Water Safety and Water Efficiency (2015 edition incorporating 2016 amendments).
Hot Water Temperature Requirements (AD-G Section G3)
| Parameter | Requirement | Reason |
|---|---|---|
| Storage temperature | ≥ 60°C | Legionella prevention |
| Distribution temperature | ≥ 55°C at return / furthest point | Prevent bacterial growth in pipework |
| Bath outlet (new dwellings) | ≤ 48°C (via TMV) | Scald prevention |
| High-limit cut-out | ~90°C (non-self-resetting) | Over-temperature safety |
| T&P relief valve | 90-95°C / 6-10 bar | Pressure and temperature safety |
Legionella Temperature Risk Zones
| Temperature Range | Risk Level | Notes |
|---|---|---|
| Below 20°C | Low — bacteria dormant | Cold water should be kept below 20°C |
| 20°C to 45°C | High — rapid multiplication | Danger zone: avoid water sitting in this range |
| 45°C to 50°C | Moderate — some bacteria survive | Not hot enough to reliably kill bacteria |
| 50°C to 60°C | Low — bacteria die slowly | Takes hours to kill; not sufficient for storage |
| Above 60°C | Very low — bacteria killed quickly | Storage temperature target for safety |
Unvented Cylinder Safety Devices (AD-G Diagram 1)
| Device | Function | Standard |
|---|---|---|
| Thermostat | Controls operating temperature (60-65°C) | Integral to cylinder |
| High-limit thermal cut-out | Shuts off heat at ~90°C, requires manual reset | Non-self-resetting |
| Temperature & pressure relief valve | Opens at 90-95°C or 6-10 bar | BS 6283-2 |
| Expansion vessel / air gap | Accommodates water expansion when heated | Sized for cylinder volume |
| Tundish | Visible air break in T&P valve discharge | Within 500 mm of valve |
| Discharge pipe | Safely routes T&P discharge to safe point | Min. 1 pipe size larger than valve outlet |
G3 Notification Requirements
| Work Type | Notifiable? | Route |
|---|---|---|
| New unvented cylinder > 15 litres | Yes | Building Control or competent person scheme |
| Replacement unvented cylinder (like-for-like) | Yes | Building Control or competent person scheme |
| Vented cylinder installation | No (unless other notifiable work) | N/A |
| Unvented cylinder ≤ 15 litres | No | N/A (e.g. under-sink heaters) |
Related Calculators
Use the Hot Water Cylinder Calculator for sizing, or the Pipe Sizing Calculator for distribution pipework.
Always check the latest edition of Approved Documents on the Planning Portal (planningportal.co.uk) as regulations are updated periodically.
Frequently Asked Questions
Related Calculators
Water Velocity Standards
Maximum water velocities by pipe material for UK plumbing and heating. Noise thresholds and water hammer prevention.
Part H Drainage Gradients
AD-H drainage gradients: minimum falls for foul and surface water pipes, inspection chamber spacing, and bedding classes.
Part K Stair Dimensions
AD-K stair dimensions: max rise 220mm, min going 220mm, pitch max 42°, headroom 2.0m, handrail and guarding heights.
Part M Ramp Gradients
AD-M ramp gradients: max 1:12 for 2m going, 1:15 for 5m, 1:20 for 10m, with landing sizes and handrail heights.
Was this calculator helpful?
Last updated: April 2026
Verified against UK standards · estimates only, confirm with your supplier.