TradeCalculator.co.uk
Radiator BTU Output by Size and Type
Reference table of radiator BTU and watt outputs for single panel, double panel, and column radiators at standard Delta T 50 conditions.
Type 11 (Single Panel, Single Convector) at ΔT50
| Length (mm) | 400 mm high | 500 mm high | 600 mm high | 700 mm high |
|---|---|---|---|---|
| 600 | 382 W / 1,303 BTU | 478 W / 1,631 BTU | 574 W / 1,959 BTU | 669 W / 2,283 BTU |
| 800 | 509 W / 1,737 BTU | 637 W / 2,174 BTU | 765 W / 2,611 BTU | 893 W / 3,047 BTU |
| 1000 | 637 W / 2,174 BTU | 796 W / 2,717 BTU | 956 W / 3,262 BTU | 1,115 W / 3,804 BTU |
| 1200 | 764 W / 2,607 BTU | 955 W / 3,260 BTU | 1,147 W / 3,914 BTU | 1,338 W / 4,565 BTU |
| 1400 | 891 W / 3,041 BTU | 1,115 W / 3,804 BTU | 1,338 W / 4,565 BTU | 1,561 W / 5,327 BTU |
Type 22 (Double Panel, Double Convector) at ΔT50
| Length (mm) | 400 mm high | 500 mm high | 600 mm high | 700 mm high |
|---|---|---|---|---|
| 600 | 644 W / 2,198 BTU | 818 W / 2,792 BTU | 993 W / 3,389 BTU | 1,168 W / 3,986 BTU |
| 800 | 859 W / 2,931 BTU | 1,091 W / 3,723 BTU | 1,324 W / 4,518 BTU | 1,557 W / 5,313 BTU |
| 1000 | 1,074 W / 3,665 BTU | 1,364 W / 4,654 BTU | 1,655 W / 5,649 BTU | 1,946 W / 6,640 BTU |
| 1200 | 1,289 W / 4,399 BTU | 1,637 W / 5,586 BTU | 1,986 W / 6,778 BTU | 2,335 W / 7,967 BTU |
| 1400 | 1,503 W / 5,129 BTU | 1,909 W / 6,515 BTU | 2,317 W / 7,907 BTU | 2,724 W / 9,295 BTU |
Heat Pump Correction Factors
| Flow/Return Temp (°C) | ΔT | Output Factor | System Type |
|---|---|---|---|
| 80/60 | ΔT50 | 1.00 (100%) | Standard gas boiler |
| 70/50 | ΔT40 | 0.75 (75%) | Condensing boiler (optimised) |
| 55/45 | ΔT30 | 0.52 (52%) | High-temp heat pump |
| 45/35 | ΔT20 | 0.30 (30%) | Low-temp heat pump |
Related Calculators
Use the Radiator Sizing Calculator for room-by-room sizing, or the Heat Loss Calculator for accurate heat demand. The Radiator BTU Calculator provides quick room estimates.
Next up: related pages
Frequently Asked Questions
Delta T 50 (ΔT50) is the standard test condition where the average water temperature in the radiator is 50°C above the room temperature. For example, if the room is at 20°C, the average water temperature is 70°C (flow at 80°C, return at 60°C). Most radiator manufacturers quote outputs at ΔT50. Heat pumps operate at lower temperatures (ΔT30 or ΔT20), which significantly reduces radiator output — typically to 50-60% of the ΔT50 rating.
As a rough guide for UK homes: well-insulated rooms need approximately 40-50 watts (137-170 BTU) per m², average insulation needs 60-80 watts (205-273 BTU) per m², and poorly insulated rooms need 80-100+ watts (273-341+ BTU) per m². These figures should be adjusted for room height, number of external walls, window area, and floor level. A proper heat loss calculation is always recommended.
The type number indicates panels and convector fins. Type 11 (K1) has 1 panel and 1 convector fin set. Type 21 (P+) has 2 panels and 1 convector fin set. Type 22 (K2) has 2 panels and 2 convector fin sets, giving the highest output for a given length and height. A Type 22 radiator typically produces 60-70% more heat than a Type 11 of the same dimensions.
Yes, but you will need larger radiators because heat pumps operate at lower flow temperatures (typically 35-45°C vs 60-80°C for gas boilers). At ΔT25 (heat pump conditions), a radiator produces roughly 50% of its ΔT50 output. This means you may need to double the radiator size or switch to Type 22 or column radiators to compensate. Underfloor heating is ideal for heat pumps as it works well at low flow temperatures.
1 watt = 3.412 BTU/h. To convert BTU to watts, divide by 3.412. To convert watts to BTU, multiply by 3.412. For example, a radiator rated at 5,000 BTU produces approximately 1,465 watts. UK radiator manufacturers increasingly quote both BTU and watt outputs on their specification sheets.
Was this calculator helpful?
Last updated: March 2026
Verified against UK standards · estimates only, confirm with your supplier.