Eaves Ventilation Calculator — BS 5250 Compliance

Calculate eaves ventilation to BS 5250: continuous gap (10mm or 25mm by pitch), soffit vent count, over-fascia ventilators and 5mm high-level (ridge) ventilation.

Combined eaves run (both sides for duo-pitch; the single low eave for a lean-to)

Cold roof: ≤15° needs a 25mm eaves gap, >15° needs 10mm; >35° also needs a 5mm ridge gap

Eaves-to-eaves span. A span over 10m also triggers 5mm high-level ventilation

How We Calculate This

This calculator determines the eaves ventilation provision needed to comply with BS 5250 (Management of moisture in buildings).

The formula

Eaves free area (mm²) = Eaves length (m) × Free area per metre

where a continuous slot of N mm provides N × 1,000 mm² per metre (a 10mm slot = 10,000 mm²/m).

Circular vents = Eaves free area ÷ Certified free area per vent

BS 5250:2021 requirements

  • Cold roof eaves, pitch over 15°: 10mm continuous (10,000 mm²/m)
  • Cold roof eaves, pitch 15° or less: 25mm continuous (25,000 mm²/m)
  • Warm roof eaves: 25mm continuous above the insulation
  • High-level (ridge): 5mm continuous (5,000 mm²/m), fixed regardless of pitch, required where pitch over 35°, span over 10m, or the roof is mono-pitch/lean-to (and above warm-roof insulation)
  • Lean-to / mono-pitch: eaves gap by pitch (above) at the low edge + 5mm at the high edge