Skip to content

Hearing Loop Calculator - IEC 60118-4 Cable Length & Amplifier Sizing

Calculate hearing loop cable length, amplifier power and coverage area for accessible venues.

Internal length of the room (longest side)

Internal width (shortest side) — this is the loop width

How We Calculate This

This calculator determines the cable length, amplifier power, and system type needed for a hearing loop installation compliant with IEC 60118-4 and UK Building Regulations.

Field strength target

IEC 60118-4 requires a magnetic field strength of 400 mA/m (±3dB)at the listener's ear height. The calculator determines the current needed in the loop cable to achieve this, accounting for room dimensions and metal loss factors.

System selection

Following Ampetronic's Designing Induction Loops (UP60001-13), a simple perimeter loop (cable around the room edges) is suitable for rooms up to roughly 20-25m wide where no significant metal is present. The calculator switches to a low-loss array— two interleaved sets of segment loops driven 90° out of phase — when metal in the floor restricts the usable loop width, when the room is wider than about 25m, or when spill into adjacent rooms must be controlled (a perimeter loop spills audibly up to four times its width).

Drive current and amplifier sizing

The drive current is the figure to size your amplifier on — loop amplifiers are rated in amps RMS. For a perimeter loop it is the base current (the current to reach 400 mA/m at the loop plane, read from the UP60001-13 base-current curve and equal to 0.4 × π × L × W ÷ (2√(L² + W²)) for an L × W loop) multiplied by a displacement correction (Graph 2, a function of ear height ÷ loop width) and the metal adjustment factor (section 17). For an array the base current comes from the segment width and displacement. Loop resistance uses the IEC 60228 figure for the chosen cable (2.5 mm² = 7.41 Ω/km). The amplifier power shown is the loop dissipation with headroom:

Power = I² × R × noise factor × headroom

  • I: RMS drive current to achieve 400 mA/m (IEC 60118-4)
  • R: Loop cable resistance, ohms (IEC 60228 per cable size)
  • Noise factor: Extra headroom for ambient noise above 50dB

Frequently Asked Questions

Was this calculator helpful?

Last updated: March 2026

Verified against UK standards · estimates only, confirm with your supplier.