Water Main Sizing Calculator — Pipe Size by Loading Units

Size your incoming water main using the loading units method to determine simultaneous demand, pipe diameter and residual pressure.

1.5 LU each

10 LU each

3 LU each

2 LU each

3 LU each

3 LU each

3 LU each

3 LU each

Distance from meter to property

Available pressure at water meter

Installed cost per metre of MDPE

How We Calculate This

This calculator uses the loading units method of BS 8558:2011 (the British Standard for water services for domestic use, which replaced BS 6700) to estimate simultaneous demand and size the incoming water main. Each outlet is given a loading unit (LU) value reflecting its flow and frequency of use; the LU total is converted to a probable simultaneous flow rate.

The formula

Simultaneous Demand (L/s) = 0.114 × LU^0.488

This is an empirical curve fit to the BS 8558 / CIPHE loading-units chart. It tracks the chart well in the domestic range but over-reads slightly at low loads (about +10 to +17% below 30 LU) and under-reads at high loads (about −14% at 100 LU), so check larger schemes against the full BS 8558 conversion chart.

Residual Pressure = Meter Pressure − Friction Loss − Static Head

Friction loss uses the true internal bore of MDPE SDR11 pipe (25mm OD = 20.4mm bore, 32mm OD = 26.0mm bore) — MDPE is sized by outside diameter, so the bore is smaller than the nominal figure. Static head is 0.1 bar per metre of height above the meter.

Loading units table (BS 8558 / CIPHE, medium frequency)

  • WH Basin: 1.5 LU
  • Bath: 10 LU
  • Shower: 3 LU
  • WC: 2 LU
  • Kitchen sink: 3 LU

LU values follow the BS 8558 / CIPHE domestic (medium usage-frequency) band. Some design guides assign slightly different values (e.g. basin 2, kitchen sink 5); confirm against the chart for your assumed usage frequency.

Frequently Asked Questions

Was this calculator helpful?

Last updated: March 2026

Verified against UK standards · estimates only, confirm with your supplier.