Electric Shower Calculator — Cable Size & MCB Rating
Calculate the correct cable size and MCB rating for an electric shower installation, including voltage drop check per BS 7671. Covers 7kW to 12kW showers.
Check shower nameplate (7-12kW typical)
Consumer unit to shower unit
How We Calculate This
This calculator determines the MCB rating, cable size, and voltage drop for an electric shower circuit based on BS 7671 18th Edition requirements.
Formulas
Current (A) = Power (W) ÷ Voltage (V)
Voltage drop (V) = (mV/A/m × I × L) ÷ 1000
Typical Shower Circuits
- 7.5kW: 33A — 6mm² cable, 32A MCB
- 8.5kW: 37A — 10mm² cable, 40A MCB
- 9.5kW: 41A — 10mm² cable, 45A MCB
- 10.8kW: 47A — 16mm² cable, 50A MCB
- Voltage drop limit: 5% (11.5V on 230V supply)
Frequently Asked Questions
Related Calculators
Cable Sizing Calculator
Calculate the correct cable size based on BS 7671 18th Edition regulations.
Voltage Drop Calculator
Check voltage drop complies with UK wiring regulations.
Maximum Demand Calculator
Calculate maximum electrical demand for domestic installations.
Circuit Breaker Sizing Calculator
Determine the correct MCB rating for your circuit.
Socket Spacing Calculator
Plan socket layouts with Part P guidance on spacing and positioning.
Last updated: March 2026
All calculations are estimates. Verify with your supplier.