TradeCalculator.co.uk
Maximum Demand Calculator — BS 7671 Diversity
Calculate the maximum electrical demand for a domestic installation using BS 7671 diversity factors. Determine the correct main fuse or incomer size.
Number of lighting circuits (typically 6A MCB each)
32A ring finals for socket outlets
20A radial circuits
Total cooker rating in kilowatts
Adds 5A to the cooker diversity calculation per IET On-Site Guide Table A2 (only when the cooker switch incorporates a socket-outlet)
Shower rating (8.5kW, 9.5kW, 10.5kW typical)
Thermostatic water heaters take no diversity (100%) per Table A2. Typically 3kW. Fixed space/panel/storage heating is not covered by this tool — add it separately at 100% up to 10A + 50% of the excess (Table A2 ‘heating and power’ row).
3.6kW, 7kW, or 22kW typical
How We Calculate This
This calculator applies the diversity allowances from the IET On-Site Guide (BS 7671:2018+A2:2022), Appendix A, Table A2, to estimate the maximum demand of a domestic electrical installation. (Assumed current demands come from Table A1.) Maximum demand is always less than the total connected load because not all circuits operate at full capacity simultaneously.
Diversity allowances used (Table A2)
- Lighting: 66% of total connected lighting load
- Socket-outlets (rings and radials combined): 100% of the current demand of the largest circuit + 40% of the current demand of every other circuit (32A per ring final, 20A per radial)
- Cooker: First 10A at 100%, remainder at 30%, plus 5A if the control unit incorporates a socket-outlet
- Electric shower / instantaneous water heater: 100% — no diversity (single high-demand load)
- Immersion heater (thermostatic water heater): 100% — no diversity
- EV charger: 100% — continuous load, no diversity (BS 7671 Section 722)
Note: socket-outlet circuits are a single category — only the largest of all your ring and radial circuits is taken at 100%; every other one (ring or radial) is taken at 40%. Fixed space/panel/storage heating is not a field here; add it separately at 100% up to 10A plus 50% of the excess (Table A2 ‘heating and power’ row).
The calculation
Maximum Demand = Sum of all diversified circuit loads
The total is compared against standard UK main fuse ratings (60A, 80A, 100A) to recommend the appropriate incomer size. All calculations use 230V as the UK nominal supply voltage per BS 7671. Diversity is an estimating aid — final supply sizing and any DNO notification must be confirmed by the installation designer.
Frequently Asked Questions
Related Calculators
Electrical Load Calculator
Calculate the total electrical load for a domestic property.
Diversity Calculator
Apply BS 7671 diversity factors to calculate maximum demand for DNO supply applications.
Smart Meter CT Calculator
Select CT ratios and secondary wiring for smart meter installations by maximum demand.
Earth Fault Loop Impedance Calculator
Calculate Zs from Ze and R1+R2 values and validate against BS 7671 maximum Zs tables.
Was this calculator helpful?
Last updated: February 2026
Verified against UK standards · estimates only, confirm with your supplier.