Skip to content

Electric Shower Calculator — Cable Size & MCB Rating

Calculate the correct cable size and MCB rating for an electric shower installation, including voltage drop check per BS 7671. Covers 7kW to 12kW showers.

Check shower nameplate (7-12kW typical)

Consumer unit to shower unit

Safety notice

Electrical work in dwellings can be notifiable under Part P of the Building Regulations. Treat these figures as planning guidance only: circuits must be designed, installed and certified to BS 7671 by a competent person, normally a registered electrician.

How We Calculate This

This calculator determines the MCB rating, cable size, and voltage drop for an electric shower circuit based on BS 7671:2018+A2:2022 (18th Edition, Amendment 2) requirements.

Formulas

Current (A) = Power (W) ÷ Voltage (V)

Voltage drop (V) = (mV/A/m × I × L) ÷ 1000

Typical Shower Circuits

  • 7.0kW: 30A — 6mm² cable, 32A MCB
  • 7.5kW: 33A — 10mm² cable, 40A MCB
  • 8.5kW: 37A — 10mm² cable, 40A MCB
  • 9.5kW: 41A — 10mm² cable, 45A MCB
  • 10.8kW: 47A — 16mm² cable, 50A MCB
  • 12.0kW: 52A — 16mm² cable, 63A MCB
  • Voltage drop limit: 5% (11.5V on 230V supply)

Showers of 8kW and above are run in 10mm² as standard: although 6mm² is rated 47A clipped direct (Reference Method C), shower runs usually pass through loft insulation or above a ceiling, where BS 7671 Table 4D5 Reference Method 100 derates 6mm² to 27A (insulation up to 100mm) and Method 101 to 22A (insulation over 100mm) — below a 40A or 45A MCB.

Frequently Asked Questions

Was this calculator helpful?

Last updated: March 2026

Verified against UK standards · estimates only, confirm with your supplier.