Lighting Circuit Calculator — Light Fittings Per Circuit

Calculate how many light fittings fit on a circuit. Work out fittings needed, total wattage, circuits required, and cable run estimates for UK electrical installations.

Total surface area to cover

Wattage per light fitting

Safety notice

Electrical work in dwellings can be notifiable under Part P of the Building Regulations. Treat these figures as planning guidance only: circuits must be designed, installed and certified to BS 7671 by a competent person, normally a registered electrician.

How We Calculate This

This calculator determines how many light fittings are needed for a room based on the required lux level, then works out how many lighting circuits are needed to serve them.

Fittings calculation

Total lumens = (Lux x Area) / (Utilisation Factor x Maintenance Factor)

Fittings needed = Total lumens / Lumens per fitting

Circuit calculation

Circuit capacity (W) = Rating (A) x 230V

Design load (W) = Total wattage x Diversity factor

Circuits required = Design load / Circuit capacity

Per BS 7671, the diversity factor reduces the design demand (the load the circuit must actually supply at once), not the circuit's current-carrying capacity. So diversity is applied to the load, then compared against the full 6A/10A/16A capacity — it is not used to derate that capacity.

Defaults

  • Utilisation factor: 0.6 (typical domestic room)
  • Maintenance factor: 0.8 (adjustable)
  • Diversity factor: 0.66 (BS 7671 domestic lighting)
  • LED efficacy: ~100 lumens per watt (adjustable — typical LED downlights are 80–110 lm/W; check your fitting’s datasheet)

Note: the fittings figure is a lumen-method estimate. For circuit design the IET On-Site Guide assumes a minimum 100W per lighting point regardless of LED wattage, which typically limits a 6A circuit to about 12–18 points.

Frequently Asked Questions