Lux Level Calculator — CIBSE Lumen Method

Calculate the number of light fittings needed to achieve CIBSE recommended lux levels using the lumen method. Covers offices, warehouses, retail, and domestic rooms.

CIBSE recommended lux level

Luminaire lumen output

Internal room length

Internal room width

Floor to ceiling

How We Calculate This

This calculator uses the CIBSE lumen method to determine the number of light fittings required to achieve the recommended illuminance level.

Lumen Method Formula

N = (E × A) ÷ (F × UF × MF)

Where E = lux, A = area (m²), F = lumens per fitting, UF = utilisation factor, MF = maintenance factor

Room Index

K = (L × W) ÷ (Hm × (L + W))

  • K < 1.0: Small or tall room — low UF
  • K = 1.0-2.0: Typical office/classroom
  • K > 3.0: Large open-plan — high UF