Motor Circuit Calculator — BS 7671

Size the complete motor circuit: determine FLC from motor kW, select MCB type and rating, set overload protection, choose cable size, and check voltage drop.

Three-phase 400V motor

Determines inrush and MCB type

MCC/DB to motor

How We Calculate This

This calculator sizes all components of a motor circuit from the motor kW rating, following BS 7671 requirements for motor installations.

Motor Circuit Design

  • FLC: From motor nameplate or reference tables
  • MCB: Type D for DOL/Star-Delta, Type C for VFD/soft-start
  • MCB rating: Next standard size above FLC
  • Overload: Set to 100-105% of FLC
  • Cable: Must carry MCB rating, check VD
  • VD limit: 5% total (20V on 400V three-phase)