Zs Earth Fault Loop Impedance Calculator
Calculate total earth fault loop impedance (Zs) from Ze and R1+R2, apply temperature correction, and validate against BS 7671 Table 41.2-41.4 maximum Zs values.
Measured at origin with main earth disconnected
Line + CPC resistance at ambient temperature
Determines magnetic trip multiple
Nominal current rating of the MCB
How We Calculate This
This calculator determines total earth fault loop impedance using the formula:
Zs = Ze + (R1 + R2) × Ct
Where Ct is the temperature correction factor:
Ct = 1 + 0.004 × (Operating temp - Ambient temp)
BS 7671 Maximum Zs Values
- Type B MCBs: Trip at 3-5 × In — highest Zs allowed
- Type C MCBs: Trip at 5-10 × In — half the Zs of Type B
- Type D MCBs: Trip at 10-20 × In — quarter the Zs of Type B
- 0.4s disconnection: Required for final circuits up to 63A (Table 41.1)
- 5s disconnection: Permitted for distribution circuits
- 80% rule: Measured Zs should not exceed 80% of tabulated maximum
Frequently Asked Questions
Related Calculators
Cable Sizing Calculator
Calculate the correct cable size based on BS 7671 18th Edition regulations.
Voltage Drop Calculator
Check voltage drop complies with UK wiring regulations.
Maximum Demand Calculator
Calculate maximum electrical demand for domestic installations.
Circuit Breaker Sizing Calculator
Determine the correct MCB rating for your circuit.
Socket Spacing Calculator
Plan socket layouts with Part P guidance on spacing and positioning.
Last updated: March 2026
All calculations are estimates. Verify with your supplier.