Skip to content

Zs Earth Fault Loop Impedance Calculator

Calculate total earth fault loop impedance (Zs) from Ze and R1+R2, apply temperature correction, and validate against BS 7671 Table 41.2-41.4 maximum Zs values.

Measured at origin with main earth disconnected

Line + CPC resistance at ambient temperature

Determines magnetic trip multiple

Nominal current rating of the MCB

How We Calculate This

This calculator determines total earth fault loop impedance using the formula:

Zs = Ze + (R1 + R2) × Ct

Where Ct is the temperature correction factor:

Ct = 1 + 0.004 × (Operating temp - Ambient temp)

BS 7671 Maximum Zs Values

  • Type B MCBs: Trip at 3-5 × In — highest Zs allowed
  • Type C MCBs: Trip at 5-10 × In — half the Zs of Type B
  • Type D MCBs: Trip at 10-20 × In — quarter the Zs of Type B
  • 0.4s disconnection: Required for final circuits up to 63A (Table 41.1)
  • 5s disconnection: Permitted for distribution circuits
  • 80% rule: Measured Zs should not exceed 80% of tabulated maximum

Frequently Asked Questions

Last updated: March 2026

All calculations are estimates. Verify with your supplier.