Calculate below-ground drainage for UK extensions to AD H 2015 — pipe diameter, gradient, SVP requirements, inspection chambers and build-over agreements.

Buried drain length from the extension to the connection point.

Any WC forces a ≥100mm (110mm OD) foul drain (AD H para 2.33).

How We Calculate This

This calculator sizes below-ground extension drainage using UK Building Regulations Approved Document H (2015) and the BS EN 12056-2:2000 discharge-unit method.

Discharge units and peak flow

Each appliance contributes a discharge unit (DU) value from BS EN 12056-2 Table 2, System I: WC (6 L cistern) = 2.0, washbasin = 0.5, bath = 0.8, shower (no plug) = 0.6, kitchen sink = 0.8. The peak flow is Qww = K × √(ΣDU), with K = 0.5 for a dwelling (intermittent use). A single extension bathroom (WC + basin + bath ≈ 3.3 DU) gives a peak flow of about 1 l/s, rising toward roughly 2 l/s only for larger multi-bathroom extensions.

Pipe sizing and gradient

A foul drain carrying a WC must be at least 100mm internal diameter — 110mm OD in UK practice (AD H para 2.33); other foul drains must be at least 75mm. AD H Table 6 gives a 100mm foul drain a capacity of 9.2 l/s at the recommended self-cleansing gradient of 1:40 (for flows under 1 l/s); where a WC produces a flow over 1 l/s the absolute minimum gradient is 1:80 (capacity 6.3 l/s). Surface-water drains use a minimum of 1:100. Inspection chambers go at every change of direction or gradient, at junctions, and at intervals not exceeding the AD H Table 13 spacing.

Frequently Asked Questions

Was this calculator helpful?

Last updated: March 2026

Verified against UK standards · estimates only, confirm with your supplier.