Extension Fire Safety Calculator — Part B Compliance

Determine Approved Document B means-of-escape requirements for two-storey extensions and loft conversions: when a protected stairway is required, fire doorsets, mains-powered smoke alarms and escape windows.

Storeys in the existing house before the work (basement excluded).

New first-floor habitable rooms — each needs an emergency escape window to AD B para 2.10.

Only used when a protected stairway is required (loft / 3-storey). Each such room needs a min E 20 (FD20) fire doorset.

Open plan kitchen/living
Inner room (escape through another)

How We Calculate This

This calculator applies Approved Document B Volume 1 (Dwellings) Section 2 means-of-escape rules, keyed off whether a storey floor is more than 4.5m above ground.

Key requirements

  • Protected stairway: mandatory only when a storey is above 4.5m (loft / 3 storeys, para 2.5). Two-storey work has a choice of escape windows or a protected stairway (para 2.2)
  • Fire doorsets: minimum E 20 (FD20; FD30 in practice) on rooms opening onto a protected stairway. AD B Vol 1 does not require a self-closer or cold smoke seal on these doors in a single-family house (other than the integral-garage door)
  • Smoke/heat alarms: mains-powered, interlinked, Grade D1 Category LD2 (min LD3, §1.1) to BS 5839-6 — escape route per storey + kitchen heat alarm
  • Escape windows: 0.33 m² minimum openable area, ≥450mm each dimension, bottom of opening ≤1100mm above floor (para 2.10)

Based on Approved Document B (fire safety) Volume 1: Dwellings — 2019 edition incorporating the 2020, 2022 and 2025 amendments (collated with the 2026 and 2029 amendments). Always confirm with your Building Control body for your specific layout.