Extension Steel Calculator — Beam Sizing & Padstones

Estimate structural steel beam sizes for extension openings based on span, tributary area loading and padstone requirements. Engineer design essential.

Half the span of the floor/roof bearing on each side of the beam.

How We Calculate This

This calculator estimates structural steel beam requirements using simplified loading analysis per current UK structural standards (BS EN 1990, BS EN 1991-1-1 and BS EN 1993-1-1, each with its UK National Annex — the Eurocodes that replaced the withdrawn BS 6399 / BS 5950).

Loading calculation

Characteristic dead loads (structure self-weight and finishes) and imposed loads (people, furniture, roof maintenance) are combined at the ultimate limit state per BS EN 1990 equation 6.10: 1.35 × dead + 1.5 × imposed. Load per metre on the beam = the area load × the tributary width it collects.

Beam selection

The ULS bending moment of a simply supported beam under a uniform load is M = wL²/8. The calculator picks the smallest Universal Beam (S275) whose design bending resistance Mc,Rd = 0.275 × Wpl,y (kNm, with Wpl,y in cm³) is at least M. It then checks a simple uniform-load deflection δ = 5wL⁴/384EI (E = 210 kN/mm²) against span/360 for imposed load (plastered/brittle finishes) and span/250 for total load, using the unfactored service loads, and steps up to a stiffer section if either limit is exceeded.

What this does NOT check

The indicative size assumes the beam is fully laterally restrained. It does not assess lateral-torsional buckling, web bearing/buckling, shear, connection design, notching, fire protection or any bespoke point loads — any of which can govern and require a larger section. The padstone figure is an indicative masonry bearing-stress check, not a verified padstone design. A structural engineer MUST carry out the full design and Building Control must approve it.