Fire Alarm Zone Calculator

Calculate fire alarm zones, detector quantities and sounder coverage per BS 5839-1 for commercial and residential buildings.

Total floor area of the building

Total above-ground storeys

Exit doors per storey for call point count

Affects detector coverage area

Safety notice

Fire safety measures must satisfy Approved Document B and often need building control approval. Confirm the final specification with building control or a fire engineer before relying on it.

How We Calculate This

This calculator determines fire alarm zone quantities, detector counts and sounder requirements based on BS 5839-1:2025 rules for non-domestic system design (and BS 5839-6:2019 for dwellings and sleeping premises).

How it works

  • Zones: Each zone is capped at 2000m2 and each storey is normally a separate zone — but a building under 300m2 in total may form a single zone regardless of storeys. The 60m search-distance limit and compartment boundaries can force further subdivision on large floors.
  • Detectors: Sited to the BS 5839-1:2025 Annex A maximum spacing — about 100m2 per smoke detector (10.6m grid) and 50m2 per heat detector on flat ceilings up to 6m. Partial categories (L2–L4, P2) use an indicative fraction of floor area only; the true protected area comes from the fire risk assessment. Note that BS 5839-1:2025 no longer recommends heat detectors in rooms where people sleep.
  • Call points: One at every storey and final exit, so no one travels more than 45m to reach one (estimated as one per exit per storey).
  • Sounders: Targets of 65dB(A) in general areas and 75dB(A) at the bedhead in sleeping areas. The sounder count is a rule-of-thumb estimate only — audibility must be confirmed by an on-site sound-level survey.