Calculate the number and cost of fire safety signs including exit signs, directional arrows, fire action notices and extinguisher signs per BS 5499 and the Health and Safety (Safety Signs) Regulations.

Fire exits on each floor

Average corridor length per floor — directional signs estimated at ~15m intervals (industry rule of thumb)

Base cost for standard PVC

Safety notice

Fire safety measures must satisfy Approved Document B and often need building control approval. Confirm the final specification with building control or a fire engineer before relying on it.

How We Calculate This

This calculator gives a planning estimate of fire signage from building layout. The counts are estimating heuristics — the definitive figures come from your fire risk assessment and the standards below.

Sign types

Total = Exit signs + Directional + Fire action + Equipment + Door signs

  • Exit signs: one per exit per floor (BS 5499-4 — a sign at each storey/final exit)
  • Directional: estimated at ~15m intervals along corridors. This 15m figure is an industry rule of thumb, not a code value — BS 5499-4 actually requires a sign at every change of direction, level and decision point, sized to stay legible to the next viewpoint (l = z × h)
  • Fire action notices: estimated per floor. In practice these belong at every manual call point — under BS 5839-1 a call point sits at every final exit and within 45m travel (25m in higher-hazard areas)
  • Extinguisher signs: 2 per floor as a minimum. True provision follows BS 5306-8 (roughly one extinguisher/fire point per ~200m² and per fire point), so larger floors need more
  • Fire-door signs: estimated from exit count. The real number follows the fire-door schedule (one sign per fire door)

Sleeping-risk premises

HMOs, residential blocks, hotels and care homes carry a heavier signage burden under the Regulatory Reform (Fire Safety) Order 2005 — a fire action notice on the back of every bedroom door plus denser escape signage. Choosing one of those building types adds a sleeping-risk uplift to the fire-action allowance, but these premises always need a bespoke fire risk assessment.

Frequently Asked Questions