Room Ventilation Calculator

Calculate Part F ventilation requirements: trickle vent equivalent area, extract rates for wet rooms, and purge ventilation for 4 air changes per hour.

Mechanical extract fan installed

Intermittent fan vs continuous MVHR

Ducted cooker hood adjacent to hob

ADF 2021 Table 1.1: 30 l/s if ducted hood, 60 l/s if no hood / recirculating only

Single-storey dwelling (bungalow / single-level flat)

ADF 2021 Table 1.7: habitable/kitchen EA 8,000 mm² multi-storey, 10,000 mm² single-storey

How We Calculate This

This calculator determines the ventilation requirements for rooms under Building Regulations Part F (Ventilation). It covers trickle vent sizing, mechanical extract rates, and purge ventilation capacity.

The formula

Purge rate = Room volume × 4 ACH (ADF 2021 para 1.27)
Purge opening = Floor area ÷ 20 (hinged/pivot ≥30°, sash, external door) or ÷ 10 (hinged/pivot 15–30°), per ADF 2021 Table 1.4 — windows opening <15° are not suitable
Extract rate = Part F table by room type (Tables 1.1/1.2)
Background ventilator EA(per room, ADF 2021 Table 1.7) = 8,000 mm² for habitable rooms & kitchens in a multi-storey dwelling (10,000 mm² single-storey), 4,000 mm² for bathrooms; WCs and utility rooms have no minimum

Part F extract rates (ADF 2021 Tables 1.1/1.2)

  • Kitchen: 30 l/s intermittent (cooker hood over hob) or 60 l/s elsewhere; 13 l/s continuous
  • Bathroom: 15 l/s intermittent or 8 l/s continuous
  • Utility: 30 l/s intermittent or 8 l/s continuous
  • WC: 6 l/s intermittent or 6 l/s continuous
  • Habitable rooms (living/bedroom): no minimum extract rate — rely on background & purge ventilation