Room Ventilation Calculator
Calculate Part F ventilation requirements: trickle vent equivalent area, extract rates for wet rooms, and purge ventilation for 4 air changes per hour.
Intermittent fan vs continuous MVHR
How We Calculate This
This calculator determines the ventilation requirements for rooms under Building Regulations Part F (Ventilation). It covers trickle vent sizing, mechanical extract rates, and purge ventilation capacity.
The formula
Purge rate = Room volume × 4 ACH
Purge opening = Floor area ÷ 20
Extract rate = Part F table by room type
Trickle vent EA = 8,000 mm² (habitable/kitchen) or 4,000 mm² (wet rooms) per Part F 2021 Table 5.2b
Part F extract rates
- Kitchen: 30 l/s intermittent (adjacent to hob) or 13 l/s continuous
- Bathroom: 15 l/s intermittent or 8 l/s continuous
- Utility: 30 l/s intermittent or 8 l/s continuous
- WC: 6 l/s intermittent or 6 l/s continuous