Calculate Part F ventilation requirements: extract rates by room type, whole building ventilation rate, trickle vent sizes and system selection (MEV/dMEV/MVHR).

How We Calculate This

This calculator determines ventilation requirements per Approved Document F for UK dwellings.

Extract rates (ADF 2021 Vol 1 Tables 1.1 and 1.2)

Kitchen: 30 l/s intermittent (adjacent to hob, or 60 l/s elsewhere) or 13 l/s continuous. Bathroom/en-suite: 15 l/s intermittent or 8 l/s continuous. Utility: 30 l/s intermittent or 8 l/s continuous. WC: 6 l/s.

Whole building rate

The greater of 0.3 l/s per m2 of internal floor area and the ADF Table 1.3 rate for the bedroom count (13 + 6 per bedroom: 1 bed 19, 2 bed 25, 3 bed 31, 4 bed 37, 5 bed 43 l/s). Part F sets no rate per occupant.

Working figures for this are collected in our Part F Ventilation Rates Reference reference table.