Air Change Rate Calculator — ACH to Flow Rate
Calculate required ventilation flow rates from air changes per hour (ACH) for any room type. Uses typical design ACH ranges, with Approved Document F 2021 extract rates noted for dwellings.
For per-person flow rate calculation
Leave blank to use recommended rate
Next up: related pages
How We Calculate This
This calculator converts air changes per hour (ACH) requirements into practical flow rates in litres per second (L/s) and cubic metres per hour (m³/h) for ventilation system design.
Calculation method
Flow rate (m³/h) = Room volume (m³) × ACH. The result is then converted to L/s by dividing by 3.6 (since 1 m³/h = 1000 L ÷ 3600 s = 0.2778 L/s). The ACH applied is the typical design value for the room use you select; you can override it with a custom ACH if you have a specified rate.
Typical design ACH ranges (indicative)
These are common industry design conventions and vary by source and project — use them as a starting point, not a statutory figure. By default the calculator applies a typical design value within the range shown in the result card; you can override it with a custom ACH.
- Office: 4-8 ACH (typical 6)
- Commercial kitchen: 20-30 ACH (typical 25)
- Bathroom / WC: 8-15 ACH (typical 10)
- Server / comms room: 15-20 ACH (typical 18)
- Bedroom: 1-2 ACH (typical 1.5)
- Living room: 1-2 ACH (typical 1.5)
For UK dwellings the governing requirement is an extract rate in L/s, not an ACH: Approved Document F 2021 mandates 30 L/s at the hob (or 60 L/s elsewhere) for kitchens and 15 L/s for bathrooms (intermittent). Treat the domestic ACH bands here as rough volume-equivalents only.
Frequently Asked Questions
An air change per hour (ACH) represents the number of times the entire volume of air in a room is replaced in one hour. For example, 6 ACH in a 50 m³ room means 300 m³ of fresh air is supplied every hour. Higher ACH values indicate more ventilation, which is needed in spaces with higher occupancy, heat, or moisture loads.
For dwellings the legal requirement is an extract RATE, not an ACH: Approved Document F 2021 Table 1.1 sets minimum intermittent extract of 30 L/s adjacent to the hob (ducted cooker hood over hob) or 60 L/s elsewhere in the kitchen (no hood or recirculating hood), or 13 L/s continuous (Table 1.2). A 10-15 ACH band is only a rough volume-equivalent for a domestic kitchen. Commercial kitchens are typically designed to a much higher 20-30 ACH due to greater heat, steam, and grease-laden air.
A typical design range for offices is 4-8 air changes per hour, depending on occupancy density and internal heat gains — this calculator applies 6 ACH by default and lets you override it. In practice UK office ventilation is more often sized on a fresh-air basis of about 10 L/s per person rather than a fixed ACH, so check both against your occupancy. Open-plan offices with higher heat gains tend toward the upper end of the range.
Multiply the room volume in m³ by the ACH value to get m³/h, then divide by 3.6 to convert to L/s. For example: a 60 m³ room at 6 ACH = 360 m³/h = 100 L/s. This calculator performs this conversion automatically.
ACH describes total air volume replacement including recirculated air, while fresh air rate (outdoor air) is the portion of supply air drawn from outside. Building Regulations specify minimum fresh air rates per person (typically 10 L/s), whereas ACH covers the total air movement needed for comfort and contaminant control. Both must be satisfied.