TradeCalculator.co.uk
SFP Calculator — Specific Fan Power
Calculate Specific Fan Power (SFP) and check it against the dwelling limits in the Domestic Building Services Compliance Guide (Part L). SFP = total fan watts divided by flow rate in L/s.
Electrical input power at design flow
How We Calculate This
Specific Fan Power (SFP) is the standard measure of how efficiently a fan or whole ventilation system uses electricity to move air. You calculate fan SFP by dividing the total fan input power in watts by the airflow it delivers in litres per second, giving a figure in W/(L/s). The lower the SFP, the less electricity the fan draws for the air it shifts. For dwellings the SFP limits are set by the Domestic Building Services Compliance Guide (published under Approved Document L, the energy-efficiency part of the Building Regulations) to keep ventilation systems efficient as homes get more airtight.
Formula
SFP = Total fan power (W) / Flow rate (L/s)
For a balanced system (MVHR) you add the supply and extract fan powers together and divide by the larger of the supply or extract design flow rate, because the two sides are balanced. The result is the same unit, W/(L/s).
Part F sets the air, Part L sets the fan power
These are two different things. Approved Document F sets the minimum amount of ventilation a dwelling needs, in litres per second. Approved Document L (via the Domestic Building Services Compliance Guide) limits how much electrical power the fans may use to deliver it, in watts per litre per second. SFP is a Part L energy metric — Approved Document F itself does not quote SFP figures.
Dwelling SFP limits (Domestic Building Services Compliance Guide, Part L)
- Intermittent extract fans: less than 0.5 W/(L/s)
- Continuous supply: 0.5 W/(L/s)
- Continuous extract (MEV/dMEV): not worse than 0.7 W/(L/s)
- Balanced MVHR (supply + extract with heat recovery): 1.5 W/(L/s)
SFP is verified at the design flow rate during commissioning and recorded for Building Control. It is also an input to the SAP/EPC calculation for the dwelling, where a published (or default) SFP is multiplied by an in-use factor that allows for real-world ductwork and fan settings.
How to lower an over-the-limit SFP
Specifying an EC (electronically commutated) motor instead of an AC motor is the single biggest lever and can roughly halve the SFP. Beyond that, cut system resistance: use rigid duct rather than flexible, size ducts generously, minimise bends, keep filters clean and make sure dampers are not throttling the flow.
Non-domestic (commercial) limits
Commercial systems use Table 6.9 of Approved Document L Volume 2, 2021 edition (incorporating 2023 amendments). For new buildings the maximum SFP at design flow is 2.0 W/(L/s) for a central balanced system with heating and cooling, 1.9 for heating only, and 1.5 for all other central balanced systems; local supply or extract units (such as toilet extract) are limited to 0.3 W/(L/s). Existing buildings get slightly higher allowances. Non-domestic SFP must be calculated to BS EN 16798-3 at the full design load (BS 8850 for fan coil units) — confirm the applicable band for your project.
Frequently Asked Questions
Related Calculators
dMEV Fan Calculator
Size decentralised MEV fans per room with power consumption and SFP check.
Extract Fan Sizing Calculator
Size extract fans per Part F rates with duct resistance calculation.
MEV System Calculator
Calculate centralised MEV fan duty, branch duct sizing and boost switching.
Ventilation Background Rate Calculator
Calculate Part F whole dwelling ventilation rate with trickle vent EA per room.
Was this calculator helpful?
Last updated: July 2026
Verified against UK standards · estimates only, confirm with your supplier.