Background Ventilation Calculator — Part F Trickle Vents

Calculate minimum whole dwelling ventilation rate, trickle ventilator equivalent areas per room, and purge ventilation openings per Approved Document F 2021 Tables 1.3, 1.7 and 1.4.

Sets whole-dwelling rate (Table 1.3) - 8000 mm² EA each

8000 mm² EA each

8000 mm² EA each (10,000 single-storey)

4000 mm² EA each

No ADF minimum (sanitary accommodation)

How We Calculate This

This calculator determines background ventilation requirements per Approved Document F 2021 Volume 1 for natural ventilation with intermittent extract fans and background ventilators (the approach formerly numbered System 1, before the 2021 edition replaced the numbered systems with named system types).

ADF 2021 Table 1.3 — whole dwelling rates

  • 1 bedroom: 19 L/s
  • 2 bedrooms: 25 L/s
  • 3 bedrooms: 31 L/s
  • 4 bedrooms: 37 L/s
  • 5 bedrooms: 43 L/s (add 6 L/s per extra bedroom)
  • Or 0.3 L/s per m² internal floor area (whichever is greater)

ADF 2021 Table 1.7 — trickle vent EA

  • Habitable rooms & kitchen: 8000 mm² EA each (10,000 in single-storey dwellings)
  • Bathroom: 4000 mm² EA; utility room & WC: no minimum