Skip to content

Heating Balancing Calculator — Radiator Flow Rates

Calculate the required flow rate per radiator for system balancing. Target ΔT of 11-12°C across each radiator with lock-shield Kv settings.

Whole-house boiler duty — sets the Total System Flow. The 4 radiators below are a sample circuit, so their branch flows only sum to this if every emitter is entered.

Nearest to boiler

Second nearest

Third in circuit

Furthest from boiler

How We Calculate This

Heating system balancing ensures each radiator receives the correct flow rate proportional to its heat output. This calculator determines the required flow rate and lock-shield valve setting for each radiator.

Formulas

  • Flow rate (L/min): (kW × 60) ÷ (4.186 × ΔT)
  • BTU to kW: BTU/hr × 0.000293071
  • Return temp: Flow temp − ΔT
  • Kv value (DIN EN 60534): Kv = Q(m³/h) ÷ √ΔP(bar), where Q(m³/h) = flow(L/min) × 0.06

Kv is the valve flow coefficient — the flow in m³/h that passes through the fully-open valve at a 1 bar pressure drop. The lock-shield is closed down toward this Kv to throttle each radiator's flow.

The headline Total System Flowis the boiler's whole-house duty (from the Total System Output you enter). The four radiators are a worked sample circuit, so their branch flows will only sum to the total flow if every emitter on the system has been entered — expect the sample branch flows to be smaller than the headline total.

Enter up to four radiator BTU outputs to calculate individual flow rates. Use clip-on pipe thermometers to verify the ΔT at each radiator during the balancing process. Commissioning and balancing of water-based heating systems is covered by BS EN 14336.

Frequently Asked Questions

Was this calculator helpful?

Last updated: March 2026

Verified against UK standards · estimates only, confirm with your supplier.