Skip to content

TRV Sizing Calculator — Kv & Flow Limiting

Calculate the required TRV Kv from radiator flow rate and pressure drop, check it against the valve body’s Kvs, and read the pre-set flow-limiting position from the verified Drayton TRV4 curve.

Radiator rated output (use the BTU figure at your design ΔT)

Flow−return difference (not the absolute flow temp) — this is what sets the water flow rate. 11°C typical boiler, ~5°C heat pump (MCS Heat Emitter Guide / CIBSE Domestic Heating Design Guide)

Pressure drop across the valve (domestic radiator valves ~0.05–0.15 bar)

How We Calculate This

This calculator determines the required Kv value for a thermostatic radiator valve based on the radiator's heat output and the available pressure drop across the valve.

Formulas

  • Flow rate: kW ÷ (4.186 × ΔT) = L/s (specific heat of water ≈ 4.186 kJ/kg·K)
  • Required Kv: Q (m³/hr) ÷ √ΔP (bar)
  • Body verdict: required Kv compared against the body's published Kvs(max) (Drayton TRV4 8/10/15mm body = 1.01 m³/hr)
  • Pre-set position: the lowest setting on the valve's published Kvs table whose Kvs(max) ≥ the required Kv — not a fixed step per setting

The pre-set positions shown use the verified Drayton TRV4 range Kvs(max) curve (settings 1–6 = 0.10 / 0.14 / 0.22 / 0.38 / 0.66 / 1.01 m³/hr, which is non-linear). The 8mm and 10mm sizes are the 15mm TRV4 body fitted with reducers, so they share this curve. For 22mm/28mm bodies or other valve brands, read the position from that valve's own pre-set chart.

Frequently Asked Questions

Was this calculator helpful?

Last updated: March 2026

Verified against UK standards · estimates only, confirm with your supplier.