Skip to content

System Bypass Calculator — ABV Settings

Calculate automatic bypass valve settings, minimum boiler flow rate protection, and ΔP settings for heating systems with TRVs.

Boiler rated heating output

Design flow-return temperature difference

Total TRVs on system

How We Calculate This

This calculator determines the bypass requirements for a heating system with TRVs. It calculates the minimum flow rate the boiler needs for safe operation and the correct ABV pressure differential setting.

Method

  • System flow (hydronic heat balance, CIBSE Guide G): (kW × 60) ÷ (4.186 × ΔT) L/min, where 4.186 kJ/kgK is the specific heat of water
  • Minimum flow: taken as a default ~30% of total system flow. This is only a rough estimate — the real minimum circulation flow is boiler-specific, so use the l/min figure in your boiler’s installation manual
  • Bypass ΔP (rule of thumb, not a standard): a starting point of roughly half the pump maximum head, using 1 m water ≈ 0.098 bar. Always fine-tune on commissioning per the ABV maker’s instructions (ESI / Banico / Caleffi) — open until the bypass leg just warms with TRVs closed, then back off a quarter turn
  • Pipe size: sized on the bypass flow rate

The flow formula is standard CIBSE/hydronic engineering. The bypass ΔP starting value is a practical rule of thumb, not a figure from a British Standard — the authoritative procedure is to commission the valve to the actual system, keeping the setting below the pump’s maximum head so it can still open.

Frequently Asked Questions

Was this calculator helpful?

Last updated: March 2026

Verified against UK standards · estimates only, confirm with your supplier.