Part E Acoustic Performance Standards
Airborne and impact sound insulation requirements for separating walls and floors, referencing Approved Document E: Resistance to the Passage of Sound (2003 edition incorporating 2004, 2010, 2013, and 2015 amendments).
Minimum Performance Standards (AD-E Table 0.1a & 0.1b)
| Element | Test Parameter | New Build (dB) | Conversion (dB) |
|---|---|---|---|
| Separating wall (airborne) | DnT,w + Ctr | ≥ 45 | ≥ 43 |
| Separating floor (airborne) | DnT,w + Ctr | ≥ 45 | ≥ 43 |
| Separating floor (impact) | L'nT,w | ≤ 62 | ≤ 64 |
| Wall between dwelling and common area (airborne) | DnT,w + Ctr | ≥ 43 | ≥ 43 |
| Floor between dwelling and common area (airborne) | DnT,w + Ctr | ≥ 43 | ≥ 43 |
Internal Walls and Floors Within a Dwelling (AD-E Section 3)
| Element | Requirement |
|---|---|
| Walls between bedrooms and bathrooms/WCs | Good practice guidance only (no statutory minimum) |
| Floors between rooms in dwellings formed by conversion | Rw ≥ 40 dB recommended |
| Walls between rooms and refuse chutes/lifts | See AD-E Section 4 for specific guidance |
Pre-Completion Testing (PCT) Requirements
| Requirement | Detail |
|---|---|
| When required | All new-build dwellings unless using Robust Details |
| Test standard | BS EN ISO 16283 (replaced BS EN ISO 140) |
| Sample rate (first dwelling type) | 1 set of tests per dwelling type per site |
| If test fails | Remedial work required, then re-test |
| Tester accreditation | UKAS-accredited or registered with ANC/ATTMA scheme |
Related Calculators
Use the Sound Insulation Calculator for estimating acoustic performance. See the Part E Sound Reduction page for wall and floor construction specifications.
Always check the latest edition of Approved Documents on the Planning Portal (planningportal.co.uk) as regulations are updated periodically.
Frequently Asked Questions
Related Calculators
Part L U-Value Targets History
Part L U-value requirements from 2006 to 2021: walls, floors, roofs, windows and doors targets by edition year.
Insulation U-Values
Part L target U-values for walls, floors, roofs and windows with insulation thicknesses to achieve compliance.
Part B Fire Resistance Ratings
AD-B fire resistance periods: 30, 60, 90, 120 min ratings by building type for walls, floors, doors and structural elements.
Part E Sound Reduction
Part E compliant wall and floor constructions: Robust Details types, Rw ratings, and specifications for separating elements.
Was this calculator helpful?
Last updated: April 2026
Verified against UK standards · estimates only, confirm with your supplier.