UK Cavity Tray Types & Specifications
Cavity tray DPC types, widths, weep hole spacing and installation requirements for UK cavity wall construction.
Cavity Tray Types
| Type | Application | Material | Notes |
|---|---|---|---|
| Horizontal tray | Above lintels, base of cavity | Polypropylene / lead composite | Must span full cavity width + both leaves |
| Stepped tray | Roof abutments (pitched roof to wall) | Pre-formed polypropylene | 75 mm steps to match brick coursing |
| Catchment tray | Below openings (sills) | Polypropylene | Collects water running down cavity |
| Caverntray | Ridge abutments, parapet walls | Pre-formed rigid plastic | For complex junction details |
| Perpend weep vent | Weep holes in outer leaf | Plastic insert | Max 450 mm centres along tray |
Tray Width Requirements
| Cavity Width (mm) | Min. Tray Width (mm) | Notes |
|---|---|---|
| 50 | ~300 | Must extend min. 100 mm into each leaf |
| 75 | ~325 | Standard domestic cavity |
| 100 | ~350 | Wide cavity with full-fill insulation |
| 150 | ~400 | Wide cavity with thick insulation |
Key Installation Rules
- Cavity trays must slope toward the outer leaf at a minimum fall of 1:12
- Stop ends must be fitted at each end of the tray to prevent water running off the sides
- Weep holes at maximum 450 mm centres (every other perpend in stretcher bond)
- Trays must project 5 mm beyond outer face or use weep vents
- Minimum 150 mm upstand on the inner leaf side
- Laps between tray sections: minimum 100 mm, sealed with compatible adhesive
Related Calculators
See the DPC Specifications for damp proof course types, or the UK Lintel Sizes for lintel specifications above openings.
Frequently Asked Questions
Related Calculators
Related Calculators
Weep Hole Spacing
Weep hole spacing at DPC and cavity tray levels. Types, positions and maximum spacing for UK cavity walls.
UK DPC Specifications
DPC types, widths and placement rules per Approved Document C for UK building construction.
Fixings Guide by Wall Type
Fixing types and pull-out loads by wall material: brick, block, plasterboard, timber and concrete.
Part E Sound Reduction
Part E compliant wall and floor constructions: Robust Details types, Rw ratings, and specifications for separating elements.
Was this calculator helpful?
Last updated: April 2026
Verified against UK standards 路 estimates only, confirm with your supplier.