Cavity Tray Calculator — Length, Weep Holes & Stop Ends
Calculate cavity tray length, weep hole positions and stop ends for openings in cavity masonry walls.
Clear width of the window or door opening (structural opening)
150mm minimum standard
450mm max centres
Safety notice
Structural elements must be designed or checked by a structural engineer before construction. Treat these figures as initial guidance for planning and budgeting, not a structural design.
Next up: related pages
How We Calculate This
This calculator determines cavity tray lengths, weep hole quantities and stop ends for openings in cavity masonry walls. Cavity trays sit in the same wall build-up as the ties that bridge the leaves — see our calculator for how many wall ties per m² the cavity wall needs, including the extra ties required at opening reveals.
Tray length
Tray Length = Opening Width + (Extension x 2)
Standard extension: 150mm each side. Stop ends: 2 per opening.
Weep holes
Weep Holes = ceil(Opening Width / Spacing) + 1
Minimum 2 per opening (one each end). Maximum spacing 450mm.
Working figures for this are collected in our UK Cavity Tray Types & Specifications reference table.
Frequently Asked Questions
A cavity tray should extend at least 150mm beyond each side of the opening. So tray length = opening width + 300mm (150mm each side). This ensures water collected in the tray drains via the weep holes and doesn't bypass the tray at the edges. Stop ends prevent water running off the tray ends into the cavity.
Weep holes are required at maximum 450mm centres along the base of the cavity tray. The minimum is two weep holes per opening (one near each end), with extra intermediate weeps added so the spacing never exceeds 450mm centres (NHBC 6.1.17). Weep holes can be formed using open perpendicular joints (leaving the mortar out of one vertical joint per weep, roughly a full 65mm × 10mm perpend) or proprietary weep vents that allow water out but prevent pest entry.
Stop ends (or cavity tray closers) are placed at each end of the cavity tray to prevent water running off the end of the tray and down into the cavity below. They turn up and seal against the inner leaf. Every cavity tray installation needs two stop ends — one at each end. They are typically sold separately from the tray.
Cavity trays are required above all openings (windows, doors) in cavity walls, at abutments (where a roof meets a wall), at sills, and wherever a DPC is stepped within the cavity. They redirect any moisture that enters the cavity back to the outer leaf for drainage via weep holes. This is a Building Regulations requirement (Part C). See our DPC Calculator for damp-proof course quantities.
Cavity trays are grouped by where they are used. Horizontal (short) trays sit above lintels, ring beams and at flat-roof or horizontal abutments. Stepped trays follow the brick courses up a sloping roof abutment, intercepting water at every course. Preformed remedial/retrofit trays are inserted into an existing cavity wall a course at a time, and many lintels come with an integral DPC tray built in. Among proprietary ranges, Cavity Trays Ltd label their stepped sloping-abutment tray "Type X", their general-purpose/horizontal-abutment tray "Type G" and their remedial retrofit tray "Type E". Trays are made in self-adhesive membrane, rigid plastic/preformed and, for conservation work, lead or code-compliant alternatives.
Related Calculators
Was this calculator helpful?
Last updated: March 2026
Verified against UK standards · estimates only, confirm with your supplier.