UK Circuit Breaker Types — MCB, RCD, RCBO
MCB types B, C and D, RCD types A, AC and F, RCBO specifications and ratings from 6A to 63A per BS 7671.
MCB Trip Curves (BS EN 60898)
| Type | Magnetic Trip Range | Application | Examples |
|---|---|---|---|
| B | 3–5 x In | Domestic, commercial lighting | Sockets, lighting, immersion heater |
| C | 5–10 x In | Moderate inrush loads | Fluorescent banks, small motors, UPS |
| D | 10–20 x In | High inrush loads | Welders, transformers, X-ray, compressors |
Common MCB Ratings (Domestic)
| Rating (A) | Type | Typical Circuit | Cable Size |
|---|---|---|---|
| 6 | B | Lighting (single circuit) | 1.0 mm² or 1.5 mm² |
| 10 | B | Lighting (larger circuit) | 1.0 mm² or 1.5 mm² |
| 16 | B | Immersion heater, towel rail | 2.5 mm² |
| 20 | B | Radial socket circuit (small) | 2.5 mm² |
| 32 | B | Ring final circuit (sockets) | 2.5 mm² |
| 40 | B | Cooker circuit (small) | 6.0 mm² |
| 45 | B | Cooker circuit, shower (9.5 kW) | 6.0 mm² or 10 mm² |
| 50 | B | Large shower (10.8 kW+), cooker | 10 mm² |
RCD Types (BS EN 61008 / 61009)
| Type | Detects | Requirement | Application |
|---|---|---|---|
| AC | AC sinusoidal only | Basic (not for all loads) | Simple resistive loads only |
| A | AC + pulsating DC | Minimum for most circuits | Standard domestic circuits |
| F | AC + pulsating DC + high frequency | For VFD/inverter loads | EV chargers, VFD washing machines |
| B | AC + pulsating DC + smooth DC | 3-phase and DC applications | Some EV chargers, 3-phase supplies |
RCD Ratings
| Sensitivity (mA) | Purpose | Application |
|---|---|---|
| 30 | Personal protection (lethal shock) | All socket circuits, bathrooms, outdoor |
| 100 | Fire protection | Fire risk premises, sleeping accommodation |
| 300 | Fire protection | Fire protection on distribution boards |
Related Calculators
See the BS 7671 Circuit Guide for full domestic circuit specifications, or the UK Cable Sizes for cable current ratings.
Frequently Asked Questions
Related Calculators
Related Calculators
BS 7671 Domestic Circuit Guide
BS 7671 domestic circuit specifications: cable sizes, MCB ratings and protective devices.
Part P RCD Requirements
AD-P and BS 7671 RCD protection: 30mA requirements for socket circuits, bathrooms, outdoors, RCD types, and notification.
UK Consumer Unit Sizes
Consumer unit sizes from 6 to 24 ways, split load vs dual RCD vs RCBO board configurations.
BS 7671 18th Edition Changes
Key changes from 17th to 18th Edition wiring regulations including AFDD, SPD, RCD and EV charging requirements.
Was this calculator helpful?
Last updated: April 2026
Verified against UK standards · estimates only, confirm with your supplier.