BS 7671 Domestic Circuit Specs — Cable Sizes and MCB Ratings

Standard domestic circuit specifications per BS 7671 18th Edition: cable sizes, MCB ratings, maximum lengths, and protective device requirements.

Standard Domestic Circuits

Standard Domestic Circuits
CircuitCable SizeMCB RatingMCB TypeRCD Required
Lighting (6A)1.0 mm² or 1.5 mm²6ABYes (30 mA)
Ring final (sockets)2.5 mm²32ABYes (30 mA)
Radial (sockets, ≤50 m²)2.5 mm²20ABYes (30 mA)
Radial (sockets, ≤75 m²)4.0 mm²32ABYes (30 mA)
Immersion heater2.5 mm²16ABYes (30 mA)
Cooker (≤13.5 kW)6.0 mm²32ABYes (30 mA)
Cooker (>13.5 kW)10.0 mm²45ABYes (30 mA)
Shower (up to 9 kW)6.0 mm²40ABYes (30 mA)
Shower (9-10.8 kW)10.0 mm²45ABYes (30 mA)
Smoke/heat alarms1.0 mm² or 1.5 mm²6ABNo (dedicated circuit)
Outdoor socket2.5 mm²16A or 20ABYes (30 mA)
EV charger (7 kW)6.0 mm² or 10.0 mm²32AB or CYes (Type A or DC)

Cable Current Ratings (Clipped Direct, PVC T&E)

Cable Current Ratings (Clipped Direct, PVC T&E)
Cable Size (mm²)Clipped Direct (A)In Insulation (A)In Conduit/Trunking (A)
1.01611.513.5
1.52014.517.5
2.5272024
4.0372732
6.0473441
10.0644657
16.0856276

Values from BS 7671 Table 4D5, Installation Method C (clipped direct). Derating factors apply for grouping, ambient temperature, and thermal insulation.