Skip to content

Voltage Drop Coefficients — mV/A/m Reference

Voltage drop values (mV/A/m) for common UK cable types per BS 7671:2018 Table 4D1B-4D5B. Use to verify cable runs comply with maximum voltage drop limits.

Twin-and-Earth (T+E) — PVC 70°C Copper

Reference: BS 7671:2018 Table 4D5B. Two loaded conductors (single-phase).

Twin-and-Earth (T+E) — PVC 70°C Copper
Cable Size (mm²)mV/A/m (at 70°C)Max Run at 20A (m)*Max Run at 32A (m)*
1.044
1.52919.8
2.51831.919.9
4.01152.332.7
6.07.378.849.2
10.04.4130.781.7
16.02.8205.4128.3

* Maximum cable run assuming 5% voltage drop limit (11.5V) on a 230V single-phase supply. Lighting circuits limited to 3% (6.9V).

SWA Cable — XLPE 90°C Copper

Reference: BS 7671:2018 Table 4D4B. Two loaded conductors (single-phase).

SWA Cable — XLPE 90°C Copper
Cable Size (mm²)mV/A/m (at 90°C)Max Run at 40A (m)*
2.51915.1
4.01224.0
6.07.936.4
10.04.761.2
16.02.999.1
25.01.85155.4

Voltage Drop Limits Summary

Voltage Drop Limits Summary
Circuit TypeMax Drop (%)Max Drop at 230V (V)
Lighting36.9
Other (power, heating, etc.)511.5

Note: Refer to BS 7671:2018 + Amendment 2:2022 for definitive values. The mV/A/m values above are for standard conditions. Reactive components of voltage drop become significant for cable sizes above 25 mm² — use the tabulated r and x values separately for larger cables.

Related Pages

See the Cable Ampacity Table for current carrying capacities, and the UK Cable Sizes reference for physical cable dimensions.

Frequently Asked Questions

Was this calculator helpful?

Last updated: April 2026

Verified against UK standards · estimates only, confirm with your supplier.