TradeCalculator.co.uk
Heat Pump Pipework Calculator
Calculate flow rates, pipe sizing, and pressure drop for heat pump installations. Includes glycol flow adjustment and maximum pipe run length.
Rated heat output
HP typically 5C, boiler 11C
Longest run from HP to emitter
Next up: related pages
How We Calculate This
This calculator determines the correct pipe sizing for heat pump primary circuits based on the required flow rate, target velocity, and glycol adjustment.
Flow rate calculation
- Flow rate: Q = kW / (4.186 × delta-T) in L/s
- Glycol adjustment: +10% flow for 25% glycol, +15% for 33% (indicative installer correction)
- Pipe selection: smallest size with velocity 0.5-1.0 m/s (MCS/CIBSE max 1.0 m/s; ~0.9 m/s ideal) and friction loss ≤ 350 Pa/m
- Pressure drop: Darcy-Weisbach (Colebrook-White friction factor) over the flow + return run
Frequently Asked Questions
Flow rate (L/s) = Heat output (kW) / (4.186 x delta-T). Heat pumps typically operate at delta-T 5C (compared to 11-20C for gas boilers), resulting in much higher flow rates. A 10 kW heat pump at dT5 needs approximately 0.48 L/s (28.7 L/min), compared to 0.22 L/s for a boiler at dT11.
Adding glycol (typically 25% propylene glycol for frost protection) lowers the volumetric heat capacity by roughly 5-10% and increases viscosity. As an indicative installer correction, this calculator raises the required flow rate by 10% for 25% glycol and 15% for 33% glycol, and increases friction loss (about 10% at 25% glycol, 20% at 33%). Always confirm against your glycol manufacturer’s fluid-property data. Pipe sizes may need to increase one size.
For heat pump primary circuits, target 0.5-1.0 m/s, with around 0.9 m/s ideal for copper. MCS and CIBSE Guide B1 (2016) Table 1.A1.4 set 1.0 m/s as the maximum for copper pipes 15-50mm, because copper is prone to erosion-corrosion above this speed. Below 0.5 m/s, air may not be carried to separators. The 1.5 m/s figure sometimes quoted is a general plumbing limit, not the heat-pump limit. The higher flow rates of heat pumps often require 28mm or 35mm primary pipework. CIBSE Guide C friction-loss target is 100-300 Pa/m, with 350 Pa/m the maximum.
Heat pumps operate at a lower temperature differential (delta-T 5C vs 11-20C for boilers), so the flow rate is 2-4 times higher for the same heat output. A 10 kW ASHP typically needs 28mm primary pipework, whereas a 10 kW boiler uses 22mm. Undersized pipes cause excessive pressure drop and reduced efficiency.
The maximum pipe run depends on the available pump head and the pipe size. Most domestic heat pump circulators provide about 4-6m of head (40-60 kPa). This calculator assumes a 50 kPa (~5 m) circulator and allows only about half of that for straight-pipe friction, because fittings, the emitter or manifold, any buffer or low-loss header, and the heat pump’s own internal resistance consume the rest. On that basis a 28mm primary at heat-pump flow rates typically allows runs of around 20-40m. Longer runs may need larger pipe or a higher-head pump.
Related Calculators
Was this calculator helpful?
Last updated: March 2026
Verified against UK standards · estimates only, confirm with your supplier.