Underfloor Heating + Heat Pump Calculator
Design underfloor heating for heat pump operation at low flow temperatures. Calculate pipe lengths, circuit counts, heat output and compatibility with ASHP/GSHP systems.
How We Calculate This
This calculator designs UFH systems optimised for heat pump operation at low flow temperatures.
The formula
Heat output (W/m²) = Base output at flow temp × Floor finish factor
- 35°C flow: ~55 W/m² base (tiles)
- 40°C flow: ~70 W/m² base
- 45°C flow: ~85 W/m² base
- Pipe length = Area ÷ Spacing × 1.1
- Max circuit length: 100m
Frequently Asked Questions
Related Calculators
Air Source Heat Pump Sizing Calculator
Size air source heat pumps from whole house heat loss with defrost derating.
Ground Source Heat Pump Calculator
Calculate ground source heat pump borehole depth or trench pipe loops per kW.
Heat Pump COP Calculator
Calculate heat pump COP and seasonal COP with running cost comparison vs gas.
Heat Pump Radiator Calculator
Re-size radiators for heat pump 45C flow with de-rating factor.
Underfloor Heating Pipe Calculator
Calculate pipe lengths and spacing for underfloor heating systems.
Floor Insulation Calculator
Calculate floor insulation thickness and quantities to meet Building Regs Part L.
Last updated: March 2026
All calculations are estimates. Verify with your supplier.