Underfloor Heating + Heat Pump Calculator

Design underfloor heating for heat pump operation at low flow temperatures. Calculate pipe lengths, circuit counts, heat output and compatibility with ASHP/GSHP systems.

Total UFH area

35°C for best COP

From heat loss calculation

Materials supply cost

How We Calculate This

This calculator designs UFH systems optimised for heat pump operation at low flow temperatures.

The formula

Heat output (W/m²) = Base output at flow temp × Floor finish factor × Pipe-spacing factor

Indicative base output for a tile/screed floor at the reference 200mm pipe spacing (wet UFH delivers 50–100 W/m² per BS EN 1264-2 / Warmup; flow temperature sits a few °C above the floor and differs from the mean water temperature, so treat these as design estimates):

  • 35°C flow: ~55 W/m² base (tile, 200mm)
  • 40°C flow: ~70 W/m² base
  • 45°C flow: ~85 W/m² base
  • BS EN 1264-2 caps occupied-zone output near 100 W/m² (29°C floor surface, ~9°C floor-to-room difference)

Closer pipe spacing concentrates the pipe and raises output: at ~45°C mean water temperature on tile, output runs roughly 100 W/m² at 100mm, 85 at 150mm, 75 at 200mm and 55 at 300mm — which is why heat pumps typically use 100–150mm centres. Floor-finish factors are indicative deratings (tile 1.0, engineered wood 0.9, laminate 0.88, carpet 0.7); a carpet-plus-underlay build often exceeds the EN 1264 0.15 m²K/W covering limit and should follow the manufacturer’s derating table.

  • Pipe length = (Area ÷ Spacing) × 1.1 (approximate bend + manifold-tail wastage)
  • Max circuit length: 100m for 16mm pipe (including tails)