TradeCalculator.co.uk
Hot Water Heat Pump Calculator
Size a dedicated DHW heat pump from daily litres demand. Calculate cylinder pairing, COP at hot water temperatures, and running costs.
Blank = estimate at ~50 L/person/day
Ofgem cap Q3 2026: 26.11p/kWh
Gas/oil unit rate (Ofgem Q3 2026 gas 7.33p/kWh; oil ~8p/kWh)
55C standard, 48C with TMV
Next up: related pages
How We Calculate This
This calculator sizes a dedicated DHW heat pump based on your daily hot water consumption and compares running costs with your current water heating system.
Sizing method
- Daily demand: ~50 litres per person at 55C (industry rule of thumb; SAP/BREDEM assume nearer 36-45 L/person/day on a 10-60C basis, so 50 L is a deliberately conservative sizing figure). Override with a measured figure if you know it.
- Energy needed: Litres x 4.186 x delta-T / 3600 = kWh (water specific heat 4.186 kJ/kg.C)
- HP capacity: Sized for a ~4-hour full reheat
- Cylinder pairing: A typical pairing guide (not a standard) — 150 / 200 / 250 / 300 L bands by daily demand; size to the manufacturer’s recommendation for the chosen unit.
- COP: An indicative estimate adjusted for target temperature and ambient. Real performance is the unit’s BS EN 16147 declared COP.
- Running cost & CO2: Electricity at the Ofgem Q3 2026 cap (26.11p/kWh), gas 7.33p/kWh; carbon uses the DESNZ/DEFRA 2026 factors (grid electricity ≈0.144 kgCO2e/kWh on a consumption basis — generation 0.131 + transmission & distribution 0.013; natural gas 0.182, kerosene 0.247 kgCO2e/kWh — the 2026 set, published June 2026, cut grid intensity ~26% vs 2025).
Frequently Asked Questions
A dedicated domestic hot water (DHW) heat pump is a self-contained unit that heats water using an integrated heat pump compressor. It extracts heat from surrounding air (typically a garage or utility room) and delivers it to a built-in or connected cylinder. Units are typically 1.5-3 kW and can be retrofit without major plumbing changes.
DHW heat pumps typically declare a COP of about 2.0-3.4 when heating water to 55C, measured to BS EN 16147 (the rating standard for domestic hot water heat pumps, tested at a 10C cold-water inlet). COP is lower than for space-heating heat pumps because of the higher target temperature. It is better in warmer locations (plant or utility rooms) and when heating to lower temperatures (45-50C with thermostatic mixing valves). The COP this tool shows is an indicative estimate; use the unit’s EN 16147 declared COP for the real figure.
A typical 2 kW DHW heat pump can reheat a 200-litre cylinder from cold in approximately 4-6 hours. For daily use (partial reheat), recovery time is typically 2-3 hours. This is adequate for most households but may require scheduling for large families.
An unheated space like a garage is ideal — the heat pump extracts heat from the air, cooling and dehumidifying the space. A utility room or plant room also works. The space should be at least 20 m³ and well-ventilated. The unit produces cool, dry exhaust air which can be beneficial in summer.
Yes. An immersion heater has a COP of 1.0 (100% efficient). A DHW heat pump achieves a COP of roughly 2.0-3.0, meaning it uses around 50-66% less electricity for the same amount of hot water. At the Ofgem Q3 2026 electricity cap (26.11p/kWh) this calculator estimates an annual saving of roughly £400-540 for a family of 3-4 replacing immersion-only heating (the exact figure depends on demand, COP and your unit rate — use the result above). It also provides dehumidification in the installed space.
Was this calculator helpful?
Last updated: June 2026
Verified against UK standards · estimates only, confirm with your supplier.