Movement Joint Calculator — Spacing, Mastic & Filler Board
Calculate movement joint positions, mastic sealant and filler board for clay brick and concrete block walls.
≈ spacing(m) + 30%, in mm (PD 6697): ~16mm at 12m clay, ~8mm at 6m concrete
Depth = Width × Factor. BS EN ISO 11600 recommends W:D of 2:1 so factor 0.5 (depth = half width).
Safety notice
Structural elements must be designed or checked by a structural engineer before construction. Treat these figures as initial guidance for planning and budgeting, not a structural design.
Next up: related pages
How We Calculate This
This calculator determines the number, spacing and material quantities for movement joints in masonry walls.
Joint count
Joints = ceil(Wall Length ÷ Spacing) − 1
Clay brick: 12m, Concrete block: 6m, Calcium silicate: 7.5m (PD 6697:2019). The first joint must sit within half the spacing of any corner, and all spacings halve for freestanding, parapet or unrestrained walls.
Sealant
Mastic Depth = Joint Width × 0.5 (a 2:1 width:depth ratio per BS EN ISO 11600; the sealant depth should never exceed the joint width, as a deep narrow bead tears under movement).
A compressible filler board or backer rod with a bond-breaker fills the remainder of the joint behind the sealant. Sealant volume per joint = width × depth × height.
Working figures for this are collected in our Movement Joint Spacing reference table.
Frequently Asked Questions
Movement joint spacing depends on the masonry material: clay bricks maximum 12m centres, concrete blocks maximum 6m centres, calcium silicate blocks 7.5m centres. The first joint must be within half the spacing of any corner or return (e.g. within 6m for 12m clay centres), and all spacings halve for freestanding, parapet or unrestrained walls (PD 6697:2019). Joints should also be placed at changes in wall height, thickness or direction. Closer spacing may be needed for very exposed walls. Use our Brick Calculator or Block Calculator for wall material quantities.
Clay bricks expand slightly after manufacture (irreversible moisture expansion), so joints accommodate growth. Concrete blocks shrink as they cure (drying shrinkage), which means more joints are needed. Clay: 12m max centres for expansion. Concrete block: 6m max centres for shrinkage. This is specified in BS EN 1996-2 with the UK guidance in PD 6697:2019 (clause 6.2.6).
Movement joints in external masonry are typically 10-16mm wide. As a guide, joint width (mm) ≈ spacing (m) + 30%, so ~16mm at 12m clay centres and ~8mm at 6m concrete centres (PD 6697). The mastic sealant should be shallow and wide — its depth should be about half the joint width (e.g. 12mm wide = ~6mm deep), and in no case deeper than the joint width, per BS EN ISO 11600 and sealant manufacturer guidance. A deep, narrow bead tears under movement. A compressible filler board or backer rod with a bond-breaker fills the joint behind the sealant; the filler should be slightly wider than the joint so it stays in compression.
Use a low-modulus polyurethane or polysulphide sealant rated for +/- 25% movement. Silicone is not suitable for masonry movement joints. The sealant must adhere to both faces of the joint. Apply a bond-breaker tape at the back of the sealant to prevent three-sided adhesion, which reduces the sealant's ability to stretch.
Internal blockwork walls also need movement joints, typically at the same 6m centres for concrete blocks. Internal walls are less exposed to temperature changes, but drying shrinkage still occurs. Movement joints in internal walls are often simply filled with mastic and decorated over, as visual appearance is less critical.