Bonding Conductor Calculator — BS 7671

Determine main protective bonding conductor sizes per BS 7671 — Table 54.8 for TN-C-S (PME) supplies and the half-earthing-conductor rule (Reg 544.1.1) for TN-S and TT.

MET to bonding clamp

Your price per metre for bonding cable

Safety notice

Electrical work in dwellings can be notifiable under Part P of the Building Regulations. Treat these figures as planning guidance only: circuits must be designed, installed and certified to BS 7671 by a competent person, normally a registered electrician.

How We Calculate This

This calculator determines the required main protective bonding conductor size based on BS 7671 18th Edition (2018+A2:2022). Main bonding is sized by conductor cross-sectional area, not by the supply fuse rating — the fuse rating is shown for context only.

PME (TN-C-S) — Table 54.8, by supply neutral (PEN) CSA

  • Neutral ≤ 35mm²: 10mm² bonding
  • Neutral >35–50mm²: 16mm² bonding
  • Neutral >50–95mm²: 25mm² bonding
  • Neutral >95–150mm²: 35mm² bonding
  • Neutral >150mm²: 50mm² bonding
  • PME floor (Reg 544.1.1): never less than 10mm²

Non-PME (TN-S, TT) — Reg 544.1.1

  • Main bonding = half the earthing-conductor CSA, minimum 6mm², maximum 25mm².
  • The earthing conductor is first sized from the line conductor via Table 54.7 (line ≤16mm² → same; >16–35mm² → 16mm²; >35mm² → half).
  • Example: 25mm² tails → earthing conductor 16mm² → half = 8mm² → 10mm² bonding.

Supplementary bonding (Reg 544.2)

  • 2.5mm² copper if mechanically protected, otherwise 4mm².
  • May be omitted where Reg 415.2.2 is met (R ≤ 50V ÷ Ia).